Influencing of Current Sensors by an External Magnetic Field of a nearby Busbar
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F18%3A10239141" target="_blank" >RIV/61989100:27240/18:10239141 - isvavai.cz</a>
Výsledek na webu
<a href="https://link.springer.com/chapter/10.1007/978-3-030-14907-9_82" target="_blank" >https://link.springer.com/chapter/10.1007/978-3-030-14907-9_82</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1007/978-3-030-14907-9_82" target="_blank" >10.1007/978-3-030-14907-9_82</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Influencing of Current Sensors by an External Magnetic Field of a nearby Busbar
Popis výsledku v původním jazyce
Based on several identified erroneous current measurements using clamping current measuring transformers, a methodology for detecting the influence of near busbar magnetic field to current sensors was designed and tested. With a 600 A current in the busbar, the ammeters and current sensors showed a current of up to 11 A, even if they did not cover any conductor. The error was dependent on the position of the current sensor and also the distance. Measurement errors were detected by some sensors even more than 50 cm from the busbar. To compare individual ammeters and current sensor a method was proposed to measure and calculate relative error value in percent of current range per kiloampere of interfering busbar current.
Název v anglickém jazyce
Influencing of Current Sensors by an External Magnetic Field of a nearby Busbar
Popis výsledku anglicky
Based on several identified erroneous current measurements using clamping current measuring transformers, a methodology for detecting the influence of near busbar magnetic field to current sensors was designed and tested. With a 600 A current in the busbar, the ammeters and current sensors showed a current of up to 11 A, even if they did not cover any conductor. The error was dependent on the position of the current sensor and also the distance. Measurement errors were detected by some sensors even more than 50 cm from the busbar. To compare individual ammeters and current sensor a method was proposed to measure and calculate relative error value in percent of current range per kiloampere of interfering busbar current.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/LO1404" target="_blank" >LO1404: Trvale udržitelný rozvoj Centra ENET</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2018
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Lecture Notes in Electrical Engineering. Volume 554
ISBN
978-3-030-14906-2
ISSN
1876-1100
e-ISSN
1876-1119
Počet stran výsledku
10
Strana od-do
850-859
Název nakladatele
Springer
Místo vydání
Cham
Místo konání akce
Ostrava
Datum konání akce
11. 9. 2018
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—