Partial Discharges Pattern Analysis of Various Covered Conductors
Popis výsledku v původním jazyce
Covered conductors represents an alternative to the reinforced aluminum conductors. The E.ON Distribuce company aims to replace some of the reinforced aluminum conductors in its overhead distribution network with covered conductors. To make this distribution network as reliable as possible, the overhead powerlines will be equipped with online insulation fault detector. Problematic insulation fault detection is one of the biggest disadvantages of medium voltage covered conductors, because of the very low fault current. But during this type of faults, partial discharges activity is usually presented. Based on this knowledge, on-line partial discharges monitor was deigned at VSB - TUO to detect such insulation faults on medium voltage overhead power lines. This article describes the testing of various covered conductors from the point of partial discharge activity during high impedance faults.
Název v anglickém jazyce
Partial Discharges Pattern Analysis of Various Covered Conductors
Popis výsledku anglicky
Covered conductors represents an alternative to the reinforced aluminum conductors. The E.ON Distribuce company aims to replace some of the reinforced aluminum conductors in its overhead distribution network with covered conductors. To make this distribution network as reliable as possible, the overhead powerlines will be equipped with online insulation fault detector. Problematic insulation fault detection is one of the biggest disadvantages of medium voltage covered conductors, because of the very low fault current. But during this type of faults, partial discharges activity is usually presented. Based on this knowledge, on-line partial discharges monitor was deigned at VSB - TUO to detect such insulation faults on medium voltage overhead power lines. This article describes the testing of various covered conductors from the point of partial discharge activity during high impedance faults.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
Výsledek vznikl pri realizaci vícero projektů. Více informací v záložce Projekty.
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2020
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
2020 21st International Scientific Conference on Electric Power Engineering (EPE) : conference proceedings : 19-21 October 2020, Prague, Czech Republic
ISBN
978-1-72819-480-6
ISSN
2376-5623
e-ISSN
2376-5631
Počet stran výsledku
5
Strana od-do
1-5
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Praha
Datum konání akce
19. 10. 2020
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—