Analýza vlivu netěsností na rekuperační výměník z tepelných trubic
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21110%2F07%3A01142354" target="_blank" >RIV/68407700:21110/07:01142354 - isvavai.cz</a>
Nalezeny alternativní kódy
RIV/60460709:41310/07:20124
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Analysis of leakage influence within capillary heat pipe recuperative heat exchanger
Popis výsledku v původním jazyce
The paper analyses the leakage of air-to-air recovery heat exchanger consisting of 100 capillary thermal tubes 1.5 m long and aligned in ten rows. The operation of the recovery exchanger prototype was tested in a pigsty. The analysis focuses on how the exchanger leakage affects the heat utilisation efficiency of the air ducted from the pigsty, changes in supply/exhaust air flow rate ratio, supply air temperature, thermal output obtained, and exchanger's total thermal and mass balances. The differences of 2.7 - 14.5 % between the exchanger's measured and actual thermal efficiency according to relation (16) and those of 18.7 - 55.8 % between the exchanger's measured and actual running efficiency (13) increase as the ratio of supply and exhaust air mass flow rates increase.
Název v anglickém jazyce
Analysis of leakage influence within capillary heat pipe recuperative heat exchanger
Popis výsledku anglicky
The paper analyses the leakage of air-to-air recovery heat exchanger consisting of 100 capillary thermal tubes 1.5 m long and aligned in ten rows. The operation of the recovery exchanger prototype was tested in a pigsty. The analysis focuses on how the exchanger leakage affects the heat utilisation efficiency of the air ducted from the pigsty, changes in supply/exhaust air flow rate ratio, supply air temperature, thermal output obtained, and exchanger's total thermal and mass balances. The differences of 2.7 - 14.5 % between the exchanger's measured and actual thermal efficiency according to relation (16) and those of 18.7 - 55.8 % between the exchanger's measured and actual running efficiency (13) increase as the ratio of supply and exhaust air mass flow rates increase.
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JN - Stavebnictví
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2007
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Infrastruktura i ekologia terenow wiejskich
ISSN
1732-5587
e-ISSN
—
Svazek periodika
13
Číslo periodika v rámci svazku
3
Stát vydavatele periodika
PL - Polská republika
Počet stran výsledku
11
Strana od-do
121-131
Kód UT WoS článku
—
EID výsledku v databázi Scopus
—