Zonal and Modeling of Air Temperature Distribution in Large Glazed Spaces
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F01%3A02040921" target="_blank" >RIV/68407700:21220/01:02040921 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Zonal and Modeling of Air Temperature Distribution in Large Glazed Spaces
Popis výsledku v původním jazyce
An example of glazed space (hall) attached to the front facade of administrative building was used for the comparison of the two concepts using the simulation software ESP-r for zonal modelling and FLUENT for CFD modeling. In the zonal modelling approachthe glazed space was represented by 18 fully mixed sub-zones separated by fictitious surfaces. A nodal flow network interconnecting all the sub-zones approximated the indoor airflow. The flow network together with the energy model of the glazed space considered the conservation of mass and energy (not momentum). A two-dimensional steady-state model was considered for the CFD simulation. The boundary conditions were transferred from the ESP-r climate database. Both the zonal and CFD modelling approachesgave very similar results in terms of air temperature distribution, maximum air temperatures, and air temperature differences between the floor and the ceiling.
Název v anglickém jazyce
Zonal and Modeling of Air Temperature Distribution in Large Glazed Spaces
Popis výsledku anglicky
An example of glazed space (hall) attached to the front facade of administrative building was used for the comparison of the two concepts using the simulation software ESP-r for zonal modelling and FLUENT for CFD modeling. In the zonal modelling approachthe glazed space was represented by 18 fully mixed sub-zones separated by fictitious surfaces. A nodal flow network interconnecting all the sub-zones approximated the indoor airflow. The flow network together with the energy model of the glazed space considered the conservation of mass and energy (not momentum). A two-dimensional steady-state model was considered for the CFD simulation. The boundary conditions were transferred from the ESP-r climate database. Both the zonal and CFD modelling approachesgave very similar results in terms of air temperature distribution, maximum air temperatures, and air temperature differences between the floor and the ceiling.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2001
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of Workshop 2001
ISBN
80-01-02335-4
ISSN
—
e-ISSN
—
Počet stran výsledku
2
Strana od-do
522-523
Název nakladatele
ČVUT
Místo vydání
Praha
Místo konání akce
Praha
Datum konání akce
5. 2. 2001
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—