Dynamic Behavior of Panel Radiators - Experimental Investigation and Modeling.
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F10%3A00175376" target="_blank" >RIV/68407700:21220/10:00175376 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Dynamic Behavior of Panel Radiators - Experimental Investigation and Modeling.
Popis výsledku v původním jazyce
The research was initiated by the needs for lowering energy consumption, its main objectives - determination of time constants of radiators' heat-up and cool-down as well as simplified models of these processes - should enable further optimization of heating systems. Methods used for these tasks include experimental thermographic measurement and computer simulations. Results obtained so far are promising; thermal imaging technique makes a significant improvement in determination of mean surface temperature of a radiator. A very good agreement with experimental data was achieved for cool-down models: relative deviation from experiments less than 3 % for a model based on differential energy balance equation and about 5 % for analytical solution in a simple spreadsheet. Heat-up process is more complex but solution using transfer functions led to a relative deviation from experiments of less than 4 %.
Název v anglickém jazyce
Dynamic Behavior of Panel Radiators - Experimental Investigation and Modeling.
Popis výsledku anglicky
The research was initiated by the needs for lowering energy consumption, its main objectives - determination of time constants of radiators' heat-up and cool-down as well as simplified models of these processes - should enable further optimization of heating systems. Methods used for these tasks include experimental thermographic measurement and computer simulations. Results obtained so far are promising; thermal imaging technique makes a significant improvement in determination of mean surface temperature of a radiator. A very good agreement with experimental data was achieved for cool-down models: relative deviation from experiments less than 3 % for a model based on differential energy balance equation and about 5 % for analytical solution in a simple spreadsheet. Heat-up process is more complex but solution using transfer functions led to a relative deviation from experiments of less than 4 %.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2010
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
REHVA 10th World Congress Clima 2010
ISBN
978-975-6907-14-6
ISSN
—
e-ISSN
—
Počet stran výsledku
1
Strana od-do
—
Název nakladatele
Rehva
Místo vydání
Brussels
Místo konání akce
Antalya
Datum konání akce
9. 5. 2010
Typ akce podle státní příslušnosti
WRD - Celosvětová akce