Flow in data racks
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F14%3A00238019" target="_blank" >RIV/68407700:21220/14:00238019 - isvavai.cz</a>
Výsledek na webu
<a href="http://dx.doi.org/10.1051/epjconf/20146702070" target="_blank" >http://dx.doi.org/10.1051/epjconf/20146702070</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1051/epjconf/20146702070" target="_blank" >10.1051/epjconf/20146702070</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Flow in data racks
Popis výsledku v původním jazyce
This paper deals with the flow in data racks. The aim of this work is to find a new arrangement of elements regulating the flow in the data rack so that the aerodynamic losses and the recirculation zones were minimized. The main reason for solving this problem is to reduce the costs of data racks cooling. Another problem to be solved is a reverse flow in the servers, thus not cooled, occuring due to the underpressure in the recirculation zones. In order to solve the problem, the experimental and numerical model of 27U data rack fitted with 10 pieces of server models with a total input of 10 kW was created. Different configurations of layout of elements affecting the flow in the inlet area of the data rack were compared. Depending on the results achieved, design solutions for the improvement of existing solutions were adopted and verified by numerical simulations
Název v anglickém jazyce
Flow in data racks
Popis výsledku anglicky
This paper deals with the flow in data racks. The aim of this work is to find a new arrangement of elements regulating the flow in the data rack so that the aerodynamic losses and the recirculation zones were minimized. The main reason for solving this problem is to reduce the costs of data racks cooling. Another problem to be solved is a reverse flow in the servers, thus not cooled, occuring due to the underpressure in the recirculation zones. In order to solve the problem, the experimental and numerical model of 27U data rack fitted with 10 pieces of server models with a total input of 10 kW was created. Different configurations of layout of elements affecting the flow in the inlet area of the data rack were compared. Depending on the results achieved, design solutions for the improvement of existing solutions were adopted and verified by numerical simulations
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
BJ - Termodynamika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/TA01010184" target="_blank" >TA01010184: Výzkum a vývoj řešení rozvaděčových, chladících a transportních systémů pro datová centra</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the International Conference Experimental Fluid Mechanics 2013
ISBN
9788026053750
ISSN
2100-014X
e-ISSN
—
Počet stran výsledku
5
Strana od-do
—
Název nakladatele
EDP Sciences
Místo vydání
Les Ulis
Místo konání akce
Kutná Hora
Datum konání akce
19. 11. 2013
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
000343672100073