Bypass Flow Influence on Energy Performance of Data Center Cooling
Popis výsledku v původním jazyce
The study aims to describe the influence of bypass on cooling of the data center. In this study, both numerical and experimental methods were combined in order to describe an undesirable effect of the bypass flow; a simplified analytical procedure was also used. The paper first describes basic metrics used when defining main parameters of data center cooling. The following part describes experimental data center where individual experiments were performed. For the needs of CFD simulations, suitable boundary conditions were defined in order to get as close as possible to the real flow inside the data center, based on measurements taken. Finally, a simplified analytical solution was used. On the basis of the analytical solution, detailed information on various components of the simulated data center are applied, the information being obtained during measurement. All three approaches are compared at the end and the influence of missing blanking plugs on the overall energy performance of data center cooling is described with the help of the performed analysis
Název v anglickém jazyce
Bypass Flow Influence on Energy Performance of Data Center Cooling
Popis výsledku anglicky
The study aims to describe the influence of bypass on cooling of the data center. In this study, both numerical and experimental methods were combined in order to describe an undesirable effect of the bypass flow; a simplified analytical procedure was also used. The paper first describes basic metrics used when defining main parameters of data center cooling. The following part describes experimental data center where individual experiments were performed. For the needs of CFD simulations, suitable boundary conditions were defined in order to get as close as possible to the real flow inside the data center, based on measurements taken. Finally, a simplified analytical solution was used. On the basis of the analytical solution, detailed information on various components of the simulated data center are applied, the information being obtained during measurement. All three approaches are compared at the end and the influence of missing blanking plugs on the overall energy performance of data center cooling is described with the help of the performed analysis
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
BJ - Termodynamika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/TA01010184" target="_blank" >TA01010184: Výzkum a vývoj řešení rozvaděčových, chladících a transportních systémů pro datová centra</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2016
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
INTERNATIONAL JOURNAL of MECHANICS
ISSN
1998-4448
e-ISSN
—
Svazek periodika
10
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
10
Strana od-do
105-114
Kód UT WoS článku
—
EID výsledku v databázi Scopus
—