Moist Air State above Counterflow Wet-Cooling Tower Fill Based on Merkel, Generalised Merkel and Klimanek & Bialecky Models
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F17%3A00319972" target="_blank" >RIV/68407700:21220/17:00319972 - isvavai.cz</a>
Výsledek na webu
<a href="http://dx.doi.org/10.1063/1.5004347" target="_blank" >http://dx.doi.org/10.1063/1.5004347</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1063/1.5004347" target="_blank" >10.1063/1.5004347</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Moist Air State above Counterflow Wet-Cooling Tower Fill Based on Merkel, Generalised Merkel and Klimanek & Bialecky Models
Popis výsledku v původním jazyce
The article deals with an evaluation of moist air state above counterflow wet-cooling tower fill. The results based on Klimanek & Bialecky model are compared with results of Merkel model and generalised Merkel model. Based on the numerical simulation it is shown that temperature is predicted correctly by using generalised Merkel model in the case of saturated or supersaturated air above the fill, but the temperature is underpredicted in the case of unsaturated moist air above the fill. The classical Merkel model always under predicts temperature above the fill. The density of moist air above the fill, which is calculated using generalised Merkel model, is strongly over predicted in the case of unsaturated moist air above the fill.
Název v anglickém jazyce
Moist Air State above Counterflow Wet-Cooling Tower Fill Based on Merkel, Generalised Merkel and Klimanek & Bialecky Models
Popis výsledku anglicky
The article deals with an evaluation of moist air state above counterflow wet-cooling tower fill. The results based on Klimanek & Bialecky model are compared with results of Merkel model and generalised Merkel model. Based on the numerical simulation it is shown that temperature is predicted correctly by using generalised Merkel model in the case of saturated or supersaturated air above the fill, but the temperature is underpredicted in the case of unsaturated moist air above the fill. The classical Merkel model always under predicts temperature above the fill. The density of moist air above the fill, which is calculated using generalised Merkel model, is strongly over predicted in the case of unsaturated moist air above the fill.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20301 - Mechanical engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/TE01020036" target="_blank" >TE01020036: Pokročilé technologie pro výrobu tepla a elektřiny</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2017
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
AIP Conference Proceedings
ISBN
978-0-7354-1572-0
ISSN
—
e-ISSN
0094-243X
Počet stran výsledku
6
Strana od-do
—
Název nakladatele
American Institute of Physics Inc.
Místo vydání
—
Místo konání akce
Plzeň
Datum konání akce
13. 6. 2017
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000417391000013