Allowable surface temperature of ceiling heating based on radiant temperature asymmetry
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F24%3A00377433" target="_blank" >RIV/68407700:21220/24:00377433 - isvavai.cz</a>
Výsledek na webu
<a href="https://doi.org/10.1016/j.jobe.2024.111019" target="_blank" >https://doi.org/10.1016/j.jobe.2024.111019</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1016/j.jobe.2024.111019" target="_blank" >10.1016/j.jobe.2024.111019</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Allowable surface temperature of ceiling heating based on radiant temperature asymmetry
Popis výsledku v původním jazyce
Radiant temperature asymmetry as one of the criteria for local thermal discomfort has an influence on the practical design of the heating system, as people are most sensitive to the radiant heating of the top of the head. The paper presents the determination of the allowable surface temperature of the heated ceiling based on the theoretical calculation using the angle factors and taking into account the allowable the radiant temperature asymmetry according to the standard values of 5 and 7 K. In practice, the radiation temperature asymmetry is determined by measuring two radiant temperatures. In this paper, the measurement of radiant temperature asymmetry is measured in an experimental room with a heated ceiling and the results are compared with the theoretical calculation procedure. The paper points out the differences between the measured and calculated values of the radiant temperature asymmetry. Based on the analyses, the allowable ceiling temperatures for radiant heating have been determined for different room geometries so that the radiant temperature asymmetry for thermal comfort categories A, B is actually observed. A new correlation has been established to determine the allowable surface temperature of the radiant ceiling as a function of the angle factor between the small plane element and the ceiling. For practical use, the correlation has been adjusted for typical geometric cases without the need for calculation of angle factors. Maximum ceiling surface temperatures are graphically displayed without causing thermal discomfort. Conversely, in large rooms with a heated ceiling, the ceiling surface temperature is severely limited, precisely because of the potential for thermal discomfort due to radiant temperature asymmetry.
Název v anglickém jazyce
Allowable surface temperature of ceiling heating based on radiant temperature asymmetry
Popis výsledku anglicky
Radiant temperature asymmetry as one of the criteria for local thermal discomfort has an influence on the practical design of the heating system, as people are most sensitive to the radiant heating of the top of the head. The paper presents the determination of the allowable surface temperature of the heated ceiling based on the theoretical calculation using the angle factors and taking into account the allowable the radiant temperature asymmetry according to the standard values of 5 and 7 K. In practice, the radiation temperature asymmetry is determined by measuring two radiant temperatures. In this paper, the measurement of radiant temperature asymmetry is measured in an experimental room with a heated ceiling and the results are compared with the theoretical calculation procedure. The paper points out the differences between the measured and calculated values of the radiant temperature asymmetry. Based on the analyses, the allowable ceiling temperatures for radiant heating have been determined for different room geometries so that the radiant temperature asymmetry for thermal comfort categories A, B is actually observed. A new correlation has been established to determine the allowable surface temperature of the radiant ceiling as a function of the angle factor between the small plane element and the ceiling. For practical use, the correlation has been adjusted for typical geometric cases without the need for calculation of angle factors. Maximum ceiling surface temperatures are graphically displayed without causing thermal discomfort. Conversely, in large rooms with a heated ceiling, the ceiling surface temperature is severely limited, precisely because of the potential for thermal discomfort due to radiant temperature asymmetry.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20101 - Civil engineering
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2024
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Journal of Building Engineering
ISSN
2352-7102
e-ISSN
2352-7102
Svazek periodika
98
Číslo periodika v rámci svazku
12
Stát vydavatele periodika
GB - Spojené království Velké Británie a Severního Irska
Počet stran výsledku
16
Strana od-do
—
Kód UT WoS článku
001339344000001
EID výsledku v databázi Scopus
2-s2.0-85206680876