Calibration of Rogowski Coils with an Integrator at High Currents
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F11%3A00181968" target="_blank" >RIV/68407700:21230/11:00181968 - isvavai.cz</a>
Nalezeny alternativní kódy
RIV/00177016:_____/11:#0000424
Výsledek na webu
<a href="http://dx.doi.org/10.1109/TIM.2011.2126090" target="_blank" >http://dx.doi.org/10.1109/TIM.2011.2126090</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/TIM.2011.2126090" target="_blank" >10.1109/TIM.2011.2126090</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Calibration of Rogowski Coils with an Integrator at High Currents
Popis výsledku v původním jazyce
This paper describes the calibration of a Rogowski coil (RC) with an integrator assigned for current measurement in the range up to 30 kA at 50 Hz mains frequency. A current loop with 10 turns with a current of 3 kA was used for calibration. The magneticfield generated in this way differs from the field of one turn placed in the centre and passed with a current of 30 kA. The influence of unevenness of winding and the cross-section of the RC may cause a calibration error when using a current loop. The difference in the results between using a current loop and one turn and the measurement uncertainties are given below. Calculations of the mutual inductances of typical RCs and their uncertainties are presented in the Appendix.
Název v anglickém jazyce
Calibration of Rogowski Coils with an Integrator at High Currents
Popis výsledku anglicky
This paper describes the calibration of a Rogowski coil (RC) with an integrator assigned for current measurement in the range up to 30 kA at 50 Hz mains frequency. A current loop with 10 turns with a current of 3 kA was used for calibration. The magneticfield generated in this way differs from the field of one turn placed in the centre and passed with a current of 30 kA. The influence of unevenness of winding and the cross-section of the RC may cause a calibration error when using a current loop. The difference in the results between using a current loop and one turn and the measurement uncertainties are given below. Calculations of the mutual inductances of typical RCs and their uncertainties are presented in the Appendix.
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JB - Senzory, čidla, měření a regulace
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2011
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
IEEE Transactions on Instrumentation and Measurement
ISSN
0018-9456
e-ISSN
—
Svazek periodika
60
Číslo periodika v rámci svazku
7
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
5
Strana od-do
2434-2438
Kód UT WoS článku
000291432000045