Measurement of DC Currents in the Power Grid by Current Transformer
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F12%3A00195005" target="_blank" >RIV/68407700:21230/12:00195005 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Measurement of DC Currents in the Power Grid by Current Transformer
Popis výsledku v původním jazyce
DC currents in power grids are mainly caused by geomagnetic activity especially during magnetic storms. It is desirable to monitor these currents to prevent saturation of transformers, which may cause blackout. However, adding DC current sensors to existing installations would be very costly. We suggest to convert some of the existing current transformers to fluxgate DC current sensors by injecting AC excitation current into their secondary winding. We successfully tested this concept on 500 A current transformer. The achievable accuracy is 10% for DC currents and 1.5 % for AC currents, which is sufficient for protection and monitoring purposes. We analyze the DC current sensitivity dependence on the (changing) grid impedance, and we show that the sensitivity can be stabilized by controlling the secondary voltage component at the excitation frequency. Excitation current injected into the grid also depends on the grid impedance, but for realistic conditions it is below 2A.
Název v anglickém jazyce
Measurement of DC Currents in the Power Grid by Current Transformer
Popis výsledku anglicky
DC currents in power grids are mainly caused by geomagnetic activity especially during magnetic storms. It is desirable to monitor these currents to prevent saturation of transformers, which may cause blackout. However, adding DC current sensors to existing installations would be very costly. We suggest to convert some of the existing current transformers to fluxgate DC current sensors by injecting AC excitation current into their secondary winding. We successfully tested this concept on 500 A current transformer. The achievable accuracy is 10% for DC currents and 1.5 % for AC currents, which is sufficient for protection and monitoring purposes. We analyze the DC current sensitivity dependence on the (changing) grid impedance, and we show that the sensitivity can be stabilized by controlling the secondary voltage component at the excitation frequency. Excitation current injected into the grid also depends on the grid impedance, but for realistic conditions it is below 2A.
Klasifikace
Druh
O - Ostatní výsledky
CEP obor
JB - Senzory, čidla, měření a regulace
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2012
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů