Study of Surface Discharges on Cable Termination
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F15%3A00232564" target="_blank" >RIV/68407700:21230/15:00232564 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Study of Surface Discharges on Cable Termination
Popis výsledku v původním jazyce
Cable system breakdowns are mostly caused by some defect on cable terminations or joints. One of critical failure occurred in a photovoltaic power plant located in the Czech Republic where the cable channel with cable terminations was exposed to poor environmental conditions. The large amount of dust was accumulated on the cable surface and busbar components. The penetrating humidity, into the cable channel, condensed on its surface when the cable was unloaded. Probably, this effect was the reason of surface discharges initiation and propagation on the cable terminations. The insulation material of terminations was long-time stressed and finally the rapid degradation was accelerated. The breakdown occurred at the end and the high fault current caused the total destruction of medium voltage devices in the cable channel and in the substation. This accident led to the intensive investigation to find reasons of this serious fault. The experimental measurement in the high voltage laboratory
Název v anglickém jazyce
Study of Surface Discharges on Cable Termination
Popis výsledku anglicky
Cable system breakdowns are mostly caused by some defect on cable terminations or joints. One of critical failure occurred in a photovoltaic power plant located in the Czech Republic where the cable channel with cable terminations was exposed to poor environmental conditions. The large amount of dust was accumulated on the cable surface and busbar components. The penetrating humidity, into the cable channel, condensed on its surface when the cable was unloaded. Probably, this effect was the reason of surface discharges initiation and propagation on the cable terminations. The insulation material of terminations was long-time stressed and finally the rapid degradation was accelerated. The breakdown occurred at the end and the high fault current caused the total destruction of medium voltage devices in the cable channel and in the substation. This accident led to the intensive investigation to find reasons of this serious fault. The experimental measurement in the high voltage laboratory
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
19th International Symposium on High Voltage Engineering
ISBN
978-80-261-0477-3
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
—
Název nakladatele
University of West Bohemia
Místo vydání
Pilsen
Místo konání akce
Pilsen
Datum konání akce
23. 8. 2015
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—