Increase of Voltage Quality in Industrial Distribution Systems
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F15%3A00236502" target="_blank" >RIV/68407700:21230/15:00236502 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Increase of Voltage Quality in Industrial Distribution Systems
Popis výsledku v původním jazyce
This paper deals with the solution of the issue of exceeding the permissible levels for long-term flicker effect Plt in industrial distribution systems. Flicker effect in distribution systems is often exceeded as a result of the connection of electric arc furnaces, which exhibits high variable electrical power in-take. The article shows the benefits of measures on the steel plants, the distribution system operator and the transmission system operator. The main benefits were the installation SVC device and reconstruction of substation 220/110 kV to substation 400/110 kV. Measurements have shown that the flicker has a major impact and configuration system 110 kV. In some cases, exceeded values flicker effect, and therefore the final part of the article deals with the possibility of deployment of active filters low power.
Název v anglickém jazyce
Increase of Voltage Quality in Industrial Distribution Systems
Popis výsledku anglicky
This paper deals with the solution of the issue of exceeding the permissible levels for long-term flicker effect Plt in industrial distribution systems. Flicker effect in distribution systems is often exceeded as a result of the connection of electric arc furnaces, which exhibits high variable electrical power in-take. The article shows the benefits of measures on the steel plants, the distribution system operator and the transmission system operator. The main benefits were the installation SVC device and reconstruction of substation 220/110 kV to substation 400/110 kV. Measurements have shown that the flicker has a major impact and configuration system 110 kV. In some cases, exceeded values flicker effect, and therefore the final part of the article deals with the possibility of deployment of active filters low power.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
International Conference on Renewable Energies and Power Quality (ICREPQ?15)
ISBN
978-84-606-5436-0
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
Universidad de Vigo
Místo vydání
Vigo
Místo konání akce
La Coruna
Datum konání akce
25. 3. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—