Partial Discharge Patterns during Accelerated Aging of Medium Voltage Cable System
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F18%3A00326677" target="_blank" >RIV/68407700:21230/18:00326677 - isvavai.cz</a>
Výsledek na webu
<a href="http://dx.doi.org/10.1109/ICHVE.2018.8641847" target="_blank" >http://dx.doi.org/10.1109/ICHVE.2018.8641847</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/ICHVE.2018.8641847" target="_blank" >10.1109/ICHVE.2018.8641847</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Partial Discharge Patterns during Accelerated Aging of Medium Voltage Cable System
Popis výsledku v původním jazyce
Measurement of partial discharges (PDs) and its phase resolved patternsis one of the most important diagnostic tools for testing of electrical insulation systems. Degradation mechanisms and identification of defects in electrical insulation systems have notbeen fully cleared yet. Development of knowledge about processes of PDs changes during aging of complex insulation systems is the next desired step. This paper concerns themeasurement of thetime dependence ofphase-resolved PD (PRPD) patterns and PD parameters during combined thermal and electrical accelerated aging ofmedium voltage cable systems. Theensuing discussiontries todescribe PRPD patterns changes. A comparison with PRPD patterns measured by others on insulation samples hasbeen carried out as well. PRPD patterns could be classified into four stages in this paper. Changes in PRPD patterns couldbe linked to initialization and development of electrical treeing. Creation of electrical trees was detected on the XLPE insulation and outer semiconducting layer interface in cable terminations, confirming the weakness part of medium and high voltage cable systems.
Název v anglickém jazyce
Partial Discharge Patterns during Accelerated Aging of Medium Voltage Cable System
Popis výsledku anglicky
Measurement of partial discharges (PDs) and its phase resolved patternsis one of the most important diagnostic tools for testing of electrical insulation systems. Degradation mechanisms and identification of defects in electrical insulation systems have notbeen fully cleared yet. Development of knowledge about processes of PDs changes during aging of complex insulation systems is the next desired step. This paper concerns themeasurement of thetime dependence ofphase-resolved PD (PRPD) patterns and PD parameters during combined thermal and electrical accelerated aging ofmedium voltage cable systems. Theensuing discussiontries todescribe PRPD patterns changes. A comparison with PRPD patterns measured by others on insulation samples hasbeen carried out as well. PRPD patterns could be classified into four stages in this paper. Changes in PRPD patterns couldbe linked to initialization and development of electrical treeing. Creation of electrical trees was detected on the XLPE insulation and outer semiconducting layer interface in cable terminations, confirming the weakness part of medium and high voltage cable systems.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2018
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of 2018 IEEE International Conference on High Voltage Engineering and Application
ISBN
978-1-5386-5086-8
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
IEEE (Institute of Electrical and Electronics Engineers)
Místo vydání
—
Místo konání akce
Divani Caravel Hotel,Athens
Datum konání akce
10. 9. 2018
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000462278900022