Simulation-Aided Development of a Compact Local Ventilation Unit with the Use of CFD Analysis
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21720%2F22%3A00359080" target="_blank" >RIV/68407700:21720/22:00359080 - isvavai.cz</a>
Nalezeny alternativní kódy
RIV/68407700:21220/22:00359080
Výsledek na webu
<a href="https://doi.org/10.34641/clima.2022.194" target="_blank" >https://doi.org/10.34641/clima.2022.194</a>
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Simulation-Aided Development of a Compact Local Ventilation Unit with the Use of CFD Analysis
Popis výsledku v původním jazyce
The current emphasis on the renovation of existing buildings to meet EU energy efficiency targets brings, in addition to energy savings and related CO2 reduction, also some negative issues. One of them can be the lack of fresh air supply caused by increased air tightness of the building envelope after its insulation and renovation or change of windows. The easy solutions are decentralized units for local ventilation, which can be installed during fast renovations in selected rooms without major building modifications. Controlled ventilation then ensures the delivery of a sufficient amount of fresh air to meet current standards and, at the same time, creates a healthy and comfortable environment for occupants. The paper demonstrates the practical use of CFD simulations for the development of a new type of compact small ventilation unit for local ventilation of rooms with heat and humidity recovery. An increase in the device efficiency and a reduction in acoustic power, while maintaining its very compact dimensions, were achieved with the help of the numerical study. The paper shows the possibility of using CFD analysis during the development of new HVAC appliances. It describes the preparation of the numerical model of the device, presents the simulation approach, including the calculation settings, and discusses device optimization based on variant numerical analyses in ANSYS Fluent. The initial prototype design of the unit was optimized following the findings from the numerical analysis, and it was verified by CFD study that the proposed adjustments were appropriate and that the expected results were achieved. In a separate CFD study, the use of different types of diffusers at the air outlet from the supply duct to the room was addressed. It was recommended to use adjustable nozzles, which allow one to direct the air flow into the room according to the user's preference. Consequently, it was verified that the ventilation unit meets the hygienic noise limits, both for day operation and for night operation with reduced power.
Název v anglickém jazyce
Simulation-Aided Development of a Compact Local Ventilation Unit with the Use of CFD Analysis
Popis výsledku anglicky
The current emphasis on the renovation of existing buildings to meet EU energy efficiency targets brings, in addition to energy savings and related CO2 reduction, also some negative issues. One of them can be the lack of fresh air supply caused by increased air tightness of the building envelope after its insulation and renovation or change of windows. The easy solutions are decentralized units for local ventilation, which can be installed during fast renovations in selected rooms without major building modifications. Controlled ventilation then ensures the delivery of a sufficient amount of fresh air to meet current standards and, at the same time, creates a healthy and comfortable environment for occupants. The paper demonstrates the practical use of CFD simulations for the development of a new type of compact small ventilation unit for local ventilation of rooms with heat and humidity recovery. An increase in the device efficiency and a reduction in acoustic power, while maintaining its very compact dimensions, were achieved with the help of the numerical study. The paper shows the possibility of using CFD analysis during the development of new HVAC appliances. It describes the preparation of the numerical model of the device, presents the simulation approach, including the calculation settings, and discusses device optimization based on variant numerical analyses in ANSYS Fluent. The initial prototype design of the unit was optimized following the findings from the numerical analysis, and it was verified by CFD study that the proposed adjustments were appropriate and that the expected results were achieved. In a separate CFD study, the use of different types of diffusers at the air outlet from the supply duct to the room was addressed. It was recommended to use adjustable nozzles, which allow one to direct the air flow into the room according to the user's preference. Consequently, it was verified that the ventilation unit meets the hygienic noise limits, both for day operation and for night operation with reduced power.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20301 - Mechanical engineering
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2022
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings CLIMA2022 | 14th REHVA HVAC World Congress, 22-25 May 2022, Rotterdam
ISBN
978-94-6366-564-3
ISSN
—
e-ISSN
—
Počet stran výsledku
8
Strana od-do
97-104
Název nakladatele
TU Delft
Místo vydání
Delft
Místo konání akce
Rotterdam
Datum konání akce
22. 5. 2022
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—