Vliv napěťového a teplotního stárnutí na charakteristiky částečných výbojů ve vysokoteplotních izolantech
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F04%3APU44722" target="_blank" >RIV/00216305:26220/04:PU44722 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Effect of Voltage and Thermal Aging on the Characteristics of Partial Discharges in High-temperature Insulators
Popis výsledku v původním jazyce
One of the most important sources of insulating material degradation is the partial discharge generation process. It is therefore essential to study the effect of thermal and voltage aging on the characteristics of partial discharges in insulators intended for high-temperature applications. In this paper, a high-temperature material called thermikanit 26.000 is studied. It was subject to thermal aging at 320 ºC for 500 hours and, subsequently, voltage aging at AC voltages ranging from 3 kV to 5 kV,, the exposure times having varied from 20 to 280 hours. To study the partial discharges, a ramp voltage was applied to the specimens, and to characterize the partial discharges occurring in the specimens, the time mean value of narrow-band noise at a band-centre frequency of 390 Hz and an effective band width of 14 Hz, was selected. This characteristic appears to depend strongly on the exposure type and duration.
Název v anglickém jazyce
Effect of Voltage and Thermal Aging on the Characteristics of Partial Discharges in High-temperature Insulators
Popis výsledku anglicky
One of the most important sources of insulating material degradation is the partial discharge generation process. It is therefore essential to study the effect of thermal and voltage aging on the characteristics of partial discharges in insulators intended for high-temperature applications. In this paper, a high-temperature material called thermikanit 26.000 is studied. It was subject to thermal aging at 320 ºC for 500 hours and, subsequently, voltage aging at AC voltages ranging from 3 kV to 5 kV,, the exposure times having varied from 20 to 280 hours. To study the partial discharges, a ramp voltage was applied to the specimens, and to characterize the partial discharges occurring in the specimens, the time mean value of narrow-band noise at a band-centre frequency of 390 Hz and an effective band width of 14 Hz, was selected. This characteristic appears to depend strongly on the exposure type and duration.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
BM - Fyzika pevných látek a magnetismus
OECD FORD obor
—
Návaznosti výsledku
Projekt
Výsledek vznikl pri realizaci vícero projektů. Více informací v záložce Projekty.
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2004
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
DISEE 2004, Dielectric and Insulating Systems in Electrical Engineering
ISBN
80-227-2110-7
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
174-177
Název nakladatele
Slovak University of Technology
Místo vydání
Bratislava
Místo konání akce
Častá - Píla
Datum konání akce
8. 9. 2004
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—