Experimental Measuring of the Earth Faults Currents in MV Compensated Networks
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F10%3APU91116" target="_blank" >RIV/00216305:26220/10:PU91116 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Experimental Measuring of the Earth Faults Currents in MV Compensated Networks
Popis výsledku v původním jazyce
The MV compensated Networks in Czech Republic are operated as nonsymmetrical, that means as networks with non-transposed lines. In these networks the fault currents depend on the affected phase because the Petersen coil is tuned only for one value of earth current. The paper deals with influence of fault type on size of fault current and on the length of its transient phenomena. There are described experiments which were realized in distribution network held by E.ON Czech Republic. There were made a fewdifferent fault (low-impedance, spark gap arc, damaged MV cable, 1.6kOhm, 0.4kOhm and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means fortyeight experimental faults. During each experiment the shunting of affected phase was applied.
Název v anglickém jazyce
Experimental Measuring of the Earth Faults Currents in MV Compensated Networks
Popis výsledku anglicky
The MV compensated Networks in Czech Republic are operated as nonsymmetrical, that means as networks with non-transposed lines. In these networks the fault currents depend on the affected phase because the Petersen coil is tuned only for one value of earth current. The paper deals with influence of fault type on size of fault current and on the length of its transient phenomena. There are described experiments which were realized in distribution network held by E.ON Czech Republic. There were made a fewdifferent fault (low-impedance, spark gap arc, damaged MV cable, 1.6kOhm, 0.4kOhm and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means fortyeight experimental faults. During each experiment the shunting of affected phase was applied.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/2A-2TP1%2F051" target="_blank" >2A-2TP1/051: Zvýšení spolehlivosti a bezpečnosti elektrických sítí (Fakulta elektrotechniky a komunikačních technologií).</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2010
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the IET 10th International Conference on Developments in Power System Protection
ISBN
978-1-84919-212-5
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
1-5
Název nakladatele
IET
Místo vydání
Manchester
Místo konání akce
Manchester
Datum konání akce
29. 3. 2010
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—