The verification of shunting method for limitation of earth fault current in MV compensated networks
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F10%3APU91119" target="_blank" >RIV/00216305:26220/10:PU91119 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
The verification of shunting method for limitation of earth fault current in MV compensated networks
Popis výsledku v původním jazyce
The paper deals with verification of shunting method for limitation of earth fault current in MV compensated networks. The verification was done by experimental measuring which was realized in distribution network held by E.ON Czech Republic. There weremade a few different fault (low-impedance, spark gap arc, damaged MV cable, 1.6kOhm, 0.4kOhm and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means forty eight experimental faults. During each experiment the shunting of affected phase was applied. The first results of fault currents and voltages analysis show that after closing the shunting circuit breaker the fault current decreases practicallyto zero that means the method of connecting of affected phase to the earthing system of substation seems be very perspective for protection the point of fault.
Název v anglickém jazyce
The verification of shunting method for limitation of earth fault current in MV compensated networks
Popis výsledku anglicky
The paper deals with verification of shunting method for limitation of earth fault current in MV compensated networks. The verification was done by experimental measuring which was realized in distribution network held by E.ON Czech Republic. There weremade a few different fault (low-impedance, spark gap arc, damaged MV cable, 1.6kOhm, 0.4kOhm and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means forty eight experimental faults. During each experiment the shunting of affected phase was applied. The first results of fault currents and voltages analysis show that after closing the shunting circuit breaker the fault current decreases practicallyto zero that means the method of connecting of affected phase to the earthing system of substation seems be very perspective for protection the point of fault.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/2A-2TP1%2F051" target="_blank" >2A-2TP1/051: Zvýšení spolehlivosti a bezpečnosti elektrických sítí (Fakulta elektrotechniky a komunikačních technologií).</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2010
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the Congreso Internacional de Distribución Eléctrica
ISBN
978-987-97399-3-8
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
1-6
Název nakladatele
CIDEL
Místo vydání
Buenos Aires, Argentina
Místo konání akce
Buenos Aires, Argentina
Datum konání akce
27. 9. 2010
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—