Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F12%3APU98616" target="_blank" >RIV/00216305:26220/12:PU98616 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault
Popis výsledku v původním jazyce
The paper focuses on the evaluation of the touch voltage measured during a series of experimental measurements performed in a compensated 22 kV distribution network equipped with an automatic system for the additional earthing of the affected phase. During the experiment, a metallic earth fault was artificially created in selected dis-tribution transforming substations. Two different network extents were tested, a basic one ? 300 A ? considered by Czech technical standards as a limit value for operatinga mixed distribution network and an extent of 800 A repre-senting a maximum value of the tested network. The paper analyses the level of touch voltage with respect to the tech-nical standards in force as well as with respect to the volt-age of the increase of the substation potential during the fault for 300 A and 800 A and assesses the influence of the additional earthing of the affected phase on the level of touch voltage.
Název v anglickém jazyce
Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault
Popis výsledku anglicky
The paper focuses on the evaluation of the touch voltage measured during a series of experimental measurements performed in a compensated 22 kV distribution network equipped with an automatic system for the additional earthing of the affected phase. During the experiment, a metallic earth fault was artificially created in selected dis-tribution transforming substations. Two different network extents were tested, a basic one ? 300 A ? considered by Czech technical standards as a limit value for operatinga mixed distribution network and an extent of 800 A repre-senting a maximum value of the tested network. The paper analyses the level of touch voltage with respect to the tech-nical standards in force as well as with respect to the volt-age of the increase of the substation potential during the fault for 300 A and 800 A and assesses the influence of the additional earthing of the affected phase on the level of touch voltage.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED0014%2F01%2F01" target="_blank" >ED0014/01/01: Centrum výzkumu a využití obnovitelných zdrojů energie</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2012
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
In Proceedings of the 13th International Scientific Conference Elecric Power Engineering 2012
ISBN
978-80-214-4514-7
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
159-164
Název nakladatele
Brno university of technology
Místo vydání
Brno
Místo konání akce
Brno
Datum konání akce
23. 5. 2012
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
000321966500027