UHF system for detection and spatial localization of partial discharge in high voltage power transformers
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F15%3APU114156" target="_blank" >RIV/00216305:26220/15:PU114156 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
UHF system for detection and spatial localization of partial discharge in high voltage power transformers
Popis výsledku v původním jazyce
The article presents a new approach to the detection of a very weak electromagnetic (EM) signal, which is generated by partial discharge (PD) in a high-voltage, oil-filled power transformer. The new technique is based on the discrimination of signals with origin in outside of the transformer which are detected by external sensing head. Performed measurement process contain several different measurement modes with corresponding arrangement of sensing heads. The time-shifts of the waveforms related to transient process occurrence in the signals are the main input parameters for localization methods. In order to estimate the position of the signal source in the 3D space a minimum of four antennas has to be used, since the time of the PD is unknown.
Název v anglickém jazyce
UHF system for detection and spatial localization of partial discharge in high voltage power transformers
Popis výsledku anglicky
The article presents a new approach to the detection of a very weak electromagnetic (EM) signal, which is generated by partial discharge (PD) in a high-voltage, oil-filled power transformer. The new technique is based on the discrimination of signals with origin in outside of the transformer which are detected by external sensing head. Performed measurement process contain several different measurement modes with corresponding arrangement of sensing heads. The time-shifts of the waveforms related to transient process occurrence in the signals are the main input parameters for localization methods. In order to estimate the position of the signal source in the 3D space a minimum of four antennas has to be used, since the time of the PD is unknown.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
Výsledek vznikl pri realizaci vícero projektů. Více informací v záložce Projekty.
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of 10th International Conference on Measurement
ISBN
978-80-969672-9-2
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
237-240
Název nakladatele
Institute of Measurement Science, Slovak Academy of Science
Místo vydání
Bratislava, SK
Místo konání akce
Smolenice
Datum konání akce
25. 5. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce