Verification of the Earth Fault Location Method Based on Evaluation of Voltage Sag in Real Distribution Network
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F15%3APU114468" target="_blank" >RIV/00216305:26220/15:PU114468 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Verification of the Earth Fault Location Method Based on Evaluation of Voltage Sag in Real Distribution Network
Popis výsledku v původním jazyce
The main aim of the contribution is verification of designed principle for earth fault location in real distribution network which is based on evaluation of voltage sags recorded on secondary side of distribution transformers MV/LV. For this purpose, series of experimental measurement in real compensated MV distribution network were carried out. During the experiments, different types of earth fault (solid, arcing and impedance earth fault) were artificially ignited and all important waveforms (secondary voltages of distribution transformer, fault currents, voltages and currents at supply substation) were recorded for further analyses. These fault records were used for verification of described method. The result of the analyses is answer to question,if it is possible to use the idea of earth fault localization method in real conditions of compensated distribution network operation.
Název v anglickém jazyce
Verification of the Earth Fault Location Method Based on Evaluation of Voltage Sag in Real Distribution Network
Popis výsledku anglicky
The main aim of the contribution is verification of designed principle for earth fault location in real distribution network which is based on evaluation of voltage sags recorded on secondary side of distribution transformers MV/LV. For this purpose, series of experimental measurement in real compensated MV distribution network were carried out. During the experiments, different types of earth fault (solid, arcing and impedance earth fault) were artificially ignited and all important waveforms (secondary voltages of distribution transformer, fault currents, voltages and currents at supply substation) were recorded for further analyses. These fault records were used for verification of described method. The result of the analyses is answer to question,if it is possible to use the idea of earth fault localization method in real conditions of compensated distribution network operation.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
Výsledek vznikl pri realizaci vícero projektů. Více informací v záložce Projekty.
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
CIRED 23rd International Conference on Electricity Distribution
ISBN
—
ISSN
2032-9644
e-ISSN
—
Počet stran výsledku
5
Strana od-do
1-5
Název nakladatele
CIRED
Místo vydání
Lyon, France
Místo konání akce
Lyon
Datum konání akce
15. 6. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—