Revenue Metering of Unbalanced Prosumers in Energy Communities
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F23%3APU147488" target="_blank" >RIV/00216305:26220/23:PU147488 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/document/10040694" target="_blank" >https://ieeexplore.ieee.org/document/10040694</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/OAJPE.2023.3243385" target="_blank" >10.1109/OAJPE.2023.3243385</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Revenue Metering of Unbalanced Prosumers in Energy Communities
Popis výsledku v původním jazyce
The presence of power generating plants owned by prosumers may lead to unbalanced bidirectional energy flows at the points of connection to the relevant distribution systems. This will impact future energy communities, where appropriate metering within the community is a crucial issue for billing purposes. This paper shows that the current metrics for active energy measurement and the registration of three-phase revenue meters may fail to fairly charge unbalanced prosumers for their use of the distribution system as an inherent phase-to-phase balancer. On the other hand, it is proven here that adopting metrics based on positive sequence power/energy measurement would lead to more fair billing within the community. A comparative study was performed using a simplified but realistic model of a distribution system feeding two prosumers (i.e., an archetype of an energy community). First, representative case studies were considered. Then, a more realistic simulation of a single day of operation was conducted. The main contribution of the paper is a detailed and systematic comparison of the methods used for measuring and sorting energy into registers in revenue meters to support the ongoing discussions about fair metering within future energy communities.
Název v anglickém jazyce
Revenue Metering of Unbalanced Prosumers in Energy Communities
Popis výsledku anglicky
The presence of power generating plants owned by prosumers may lead to unbalanced bidirectional energy flows at the points of connection to the relevant distribution systems. This will impact future energy communities, where appropriate metering within the community is a crucial issue for billing purposes. This paper shows that the current metrics for active energy measurement and the registration of three-phase revenue meters may fail to fairly charge unbalanced prosumers for their use of the distribution system as an inherent phase-to-phase balancer. On the other hand, it is proven here that adopting metrics based on positive sequence power/energy measurement would lead to more fair billing within the community. A comparative study was performed using a simplified but realistic model of a distribution system feeding two prosumers (i.e., an archetype of an energy community). First, representative case studies were considered. Then, a more realistic simulation of a single day of operation was conducted. The main contribution of the paper is a detailed and systematic comparison of the methods used for measuring and sorting energy into registers in revenue meters to support the ongoing discussions about fair metering within future energy communities.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2023
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
IEEE Open Access Journal of Power and Energy
ISSN
2687-7910
e-ISSN
—
Svazek periodika
10
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
12
Strana od-do
426-437
Kód UT WoS článku
000995880200009
EID výsledku v databázi Scopus
2-s2.0-85148442492