Partial discharges in high-voltage insulation of turbogenerators
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F10%3A00503639" target="_blank" >RIV/49777513:23220/10:00503639 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Partial discharges in high-voltage insulation of turbogenerators
Popis výsledku v původním jazyce
This paper is aimed at the development of one of the main turbogenerator diagnostic methods partial discharge galvanic measuring on high-voltage stator winding insulation. For this purpose the stator slot model with inserted stator bars which, in maximalpossible measure, respect the real machine electrode configuration were constructed. Artificial defects were created on stator bar samples similar to those which may occur during the technological production process or the machine operation. Samples with a large scale of types of defects like delamination from copper stack, interlayer delamination, stress grading tape on the slot exit, defects on external corona protection in the slot part and samples with undamaged insulation were analyzed in detail.Partial discharge patterns of these defects show considerable dissimilarities. Individual measurements were analyzed and compared in term of phase distribution of measured discharge levels and count of discharge occurrence. Obtained resul
Název v anglickém jazyce
Partial discharges in high-voltage insulation of turbogenerators
Popis výsledku anglicky
This paper is aimed at the development of one of the main turbogenerator diagnostic methods partial discharge galvanic measuring on high-voltage stator winding insulation. For this purpose the stator slot model with inserted stator bars which, in maximalpossible measure, respect the real machine electrode configuration were constructed. Artificial defects were created on stator bar samples similar to those which may occur during the technological production process or the machine operation. Samples with a large scale of types of defects like delamination from copper stack, interlayer delamination, stress grading tape on the slot exit, defects on external corona protection in the slot part and samples with undamaged insulation were analyzed in detail.Partial discharge patterns of these defects show considerable dissimilarities. Individual measurements were analyzed and compared in term of phase distribution of measured discharge levels and count of discharge occurrence. Obtained resul
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)<br>S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2010
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
ICSD 2010
ISBN
978-1-4244-7944-3
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
IEEE
Místo vydání
New York
Místo konání akce
Potsdam
Datum konání akce
1. 1. 2010
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—