Partial discharge measurement at high voltage test circuit having static frequency converters
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F14%3A43924171" target="_blank" >RIV/49777513:23220/14:43924171 - isvavai.cz</a>
Výsledek na webu
<a href="http://dx.doi.org/10.1109/IPMHVC.2014.7287228" target="_blank" >http://dx.doi.org/10.1109/IPMHVC.2014.7287228</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/IPMHVC.2014.7287228" target="_blank" >10.1109/IPMHVC.2014.7287228</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Partial discharge measurement at high voltage test circuit having static frequency converters
Popis výsledku v původním jazyce
For testing of high voltage (h.v.) components under so- called unconventional frequency test conditions as h.v. - test source very often static frequency converters (SFC) were applied. A typical example for that is the testing of power transformers at higher frequency. In the past this test was provided by standardized motor- generator sets, but more and more alternative power sources having SFC- units are used. In that case the performing of sensitive diagnostic test procedure like partial discharge (pd) measurement seems to be impossible caused by vast electromagnetic disturbances which are generated by the switching part of the SFC. On the other hand the performing of such sensitive diagnostic measurement is obligatory. For overcoming of these problems two possibilities will be described in the paper. At first the EMI pulses which are coupled into the test circuit must be suppressed. Unfortunaly, because of the mostly unknown "current-way" of these disturbances, the optimal solution
Název v anglickém jazyce
Partial discharge measurement at high voltage test circuit having static frequency converters
Popis výsledku anglicky
For testing of high voltage (h.v.) components under so- called unconventional frequency test conditions as h.v. - test source very often static frequency converters (SFC) were applied. A typical example for that is the testing of power transformers at higher frequency. In the past this test was provided by standardized motor- generator sets, but more and more alternative power sources having SFC- units are used. In that case the performing of sensitive diagnostic test procedure like partial discharge (pd) measurement seems to be impossible caused by vast electromagnetic disturbances which are generated by the switching part of the SFC. On the other hand the performing of such sensitive diagnostic measurement is obligatory. For overcoming of these problems two possibilities will be described in the paper. At first the EMI pulses which are coupled into the test circuit must be suppressed. Unfortunaly, because of the mostly unknown "current-way" of these disturbances, the optimal solution
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED2.1.00%2F03.0094" target="_blank" >ED2.1.00/03.0094: Regionální inovační centrum elektrotechniky (RICE)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2014 IEEE International Power Modulator and High Voltage Conference (IPMHVC 2014)
ISBN
978-1-4673-7323-4
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
141-144
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Santa Fe, Nové Mexiko, USA
Datum konání akce
1. 6. 2014
Typ akce podle státní příslušnosti
WRD - Celosvětová akce