Ampacity of high voltage busbar connections
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F15%3A43925752" target="_blank" >RIV/49777513:23220/15:43925752 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Ampacity of high voltage busbar connections
Popis výsledku v původním jazyce
The paper analyses a connection assembly between tubular aluminium busbars. These connections are made of stranded aluminium conductors bolted with clamp joints on the tubes. The assembly is installed in high voltage substations to provide a transverse connection between lines up to 4000 A. The purpose of the paper is to present coupled electromagnetic and thermal simulations, which were made according to the recently introduced technology of dynamic line rating in operation. Increasing maximum permissible line current according to weather conditions may affect other components in the system. Besides rigid and stranded conductor busbars in the substations, the connection assembly represents a complex task, which requires taking various weather and material parameters into consideration.
Název v anglickém jazyce
Ampacity of high voltage busbar connections
Popis výsledku anglicky
The paper analyses a connection assembly between tubular aluminium busbars. These connections are made of stranded aluminium conductors bolted with clamp joints on the tubes. The assembly is installed in high voltage substations to provide a transverse connection between lines up to 4000 A. The purpose of the paper is to present coupled electromagnetic and thermal simulations, which were made according to the recently introduced technology of dynamic line rating in operation. Increasing maximum permissible line current according to weather conditions may affect other components in the system. Besides rigid and stranded conductor busbars in the substations, the connection assembly represents a complex task, which requires taking various weather and material parameters into consideration.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 19th International Symposium on High Voltage Engineering (ISH 2015)
ISBN
978-80-261-0476-6
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
1-6
Název nakladatele
Západočeská univerzita
Místo vydání
Plzeň
Místo konání akce
Plzeň, Česká republika
Datum konání akce
23. 8. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce