Breakdown behaviour of gaseous insulation with synthetic air
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F15%3A43926062" target="_blank" >RIV/49777513:23220/15:43926062 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Breakdown behaviour of gaseous insulation with synthetic air
Popis výsledku v původním jazyce
The paper deals with basic investigation of AC breakdown behaviour of gaseous insulation with synthetic air at different level of field homogeneity and gas pressure. The measurement was performed at different gas pressure ranging from 0.1 to 0.25 MPa andgap distances from 1 to 10 cm, using two electrode test- sets. The test parameters were chosen in such a way that different field types could be realized. At slight non-uniform electrical field the measured breakdown values shows a reasonable agreementto those values based on the calculation of the streamer criterion by using a relevant approximation formula for the effective ionisation coefficient. The best fit to the measured results was reached by slightly changing the parameters of the approximation formula depending on the gas pressure value. At strong inhomogeneous electrical field the calculated streamer inception voltage corresponds to the partial discharge (PD) inception voltage only. These calculated inception voltage fits t
Název v anglickém jazyce
Breakdown behaviour of gaseous insulation with synthetic air
Popis výsledku anglicky
The paper deals with basic investigation of AC breakdown behaviour of gaseous insulation with synthetic air at different level of field homogeneity and gas pressure. The measurement was performed at different gas pressure ranging from 0.1 to 0.25 MPa andgap distances from 1 to 10 cm, using two electrode test- sets. The test parameters were chosen in such a way that different field types could be realized. At slight non-uniform electrical field the measured breakdown values shows a reasonable agreementto those values based on the calculation of the streamer criterion by using a relevant approximation formula for the effective ionisation coefficient. The best fit to the measured results was reached by slightly changing the parameters of the approximation formula depending on the gas pressure value. At strong inhomogeneous electrical field the calculated streamer inception voltage corresponds to the partial discharge (PD) inception voltage only. These calculated inception voltage fits t
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/ED2.1.00%2F03.0094" target="_blank" >ED2.1.00/03.0094: Regionální inovační centrum elektrotechniky (RICE)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 19th International Symposium on High Voltage Engineering (ISH 2015)
ISBN
978-80-261-0476-6
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
1-5
Název nakladatele
Západočeská univerzita
Místo vydání
Plzeň
Místo konání akce
Plzeň, Česká republika
Datum konání akce
23. 8. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—