Frequency and voltage stability assessment of a power system during emergency service states
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F18%3A43950046" target="_blank" >RIV/49777513:23220/18:43950046 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/document/8317192" target="_blank" >https://ieeexplore.ieee.org/document/8317192</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EIConRus.2018.8317192" target="_blank" >10.1109/EIConRus.2018.8317192</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Frequency and voltage stability assessment of a power system during emergency service states
Popis výsledku v původním jazyce
Emergency service states of an electric power system such as island operation, black start or fall in to a blackout are accompanied by rapidly increased requirements of system control and ability to withstand major power, frequency and voltage changes. This paper presents an example of an electric power system (basic connection of city of Pilsen on the 110 kV voltage level) falling in to an island operation and examines influence of rapid load/generation balance changes on the system frequency and voltage. It shows advantages and threats of Rate of Change of Frequency (RoCoF) application instead of solid frequency limits for both – protection of generators and Under Frequency Load Shedding (UFLS). The paper also deals with the question of decreased frequency and its influence on the connected load.
Název v anglickém jazyce
Frequency and voltage stability assessment of a power system during emergency service states
Popis výsledku anglicky
Emergency service states of an electric power system such as island operation, black start or fall in to a blackout are accompanied by rapidly increased requirements of system control and ability to withstand major power, frequency and voltage changes. This paper presents an example of an electric power system (basic connection of city of Pilsen on the 110 kV voltage level) falling in to an island operation and examines influence of rapid load/generation balance changes on the system frequency and voltage. It shows advantages and threats of Rate of Change of Frequency (RoCoF) application instead of solid frequency limits for both – protection of generators and Under Frequency Load Shedding (UFLS). The paper also deals with the question of decreased frequency and its influence on the connected load.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2018
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2018 IEEE Conference of Russian Young Researchers in Electrical and Electronic Engineering (EIConRus)
ISBN
978-1-5386-4340-2
ISSN
—
e-ISSN
neuvedeno
Počet stran výsledku
4
Strana od-do
708-711
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
St. Petersburg, Russia
Datum konání akce
29. 1. 2018
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku