Various aging processes in a paper-natural ester insulation system in the presence of copper and moisture
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F20%3A43959026" target="_blank" >RIV/49777513:23220/20:43959026 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/document/9050518" target="_blank" >https://ieeexplore.ieee.org/document/9050518</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/ACCESS.2020.2983907" target="_blank" >10.1109/ACCESS.2020.2983907</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Various aging processes in a paper-natural ester insulation system in the presence of copper and moisture
Popis výsledku v původním jazyce
This article adds more information to the problem of natural ester use as an electroinsulating uid in cellulose paper-oil systems, e.g., for use in power transformers. An accelerated thermal aging (120, 140 and 160 C) of samples consisting of cellulose paper (transformerboard), a treated natural ester (ltered, basic Al2O3, 0.53% DBPC), a copper plate and moisture was studied. Research was especially focused on the impact of moisture on the aging of the above system. Samples with three different oil moisture levels (80, 143 and 305 ppm water content) were subjected to thermal aging to display the change in a selection of properties (tan, acid number, water content). For a study of the polarization effects, broadband dielectric spectroscopy (BDS) was performed to observe the complex permittivity and conductivity dependencies on the temperature and frequency (30 C, 0.01107 Hz). Havriliak-Negami (H-N) diagrams were used to further understand the results. The degradation products during thermal aging were recognized by Fourier transform infrared (FT-IR) spectroscopy. Hydrolysis and hydrogenation occurred in the insulating system with a natural ester aged by elevated temperatures, which is in contrast to CO2 formation in the case of electric aging. The results showed an increase in the acid number, dissipation factor, and number of hydrolysis and hydrogenation products. Furthermore, changes in polarization were observed as a consequence of the thermal aging of paper-natural ester insulation system with the presence of copper and moisture.
Název v anglickém jazyce
Various aging processes in a paper-natural ester insulation system in the presence of copper and moisture
Popis výsledku anglicky
This article adds more information to the problem of natural ester use as an electroinsulating uid in cellulose paper-oil systems, e.g., for use in power transformers. An accelerated thermal aging (120, 140 and 160 C) of samples consisting of cellulose paper (transformerboard), a treated natural ester (ltered, basic Al2O3, 0.53% DBPC), a copper plate and moisture was studied. Research was especially focused on the impact of moisture on the aging of the above system. Samples with three different oil moisture levels (80, 143 and 305 ppm water content) were subjected to thermal aging to display the change in a selection of properties (tan, acid number, water content). For a study of the polarization effects, broadband dielectric spectroscopy (BDS) was performed to observe the complex permittivity and conductivity dependencies on the temperature and frequency (30 C, 0.01107 Hz). Havriliak-Negami (H-N) diagrams were used to further understand the results. The degradation products during thermal aging were recognized by Fourier transform infrared (FT-IR) spectroscopy. Hydrolysis and hydrogenation occurred in the insulating system with a natural ester aged by elevated temperatures, which is in contrast to CO2 formation in the case of electric aging. The results showed an increase in the acid number, dissipation factor, and number of hydrolysis and hydrogenation products. Furthermore, changes in polarization were observed as a consequence of the thermal aging of paper-natural ester insulation system with the presence of copper and moisture.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/EF18_069%2F0009855" target="_blank" >EF18_069/0009855: Elektrotechnické technologie s vysokým podílem vestavěné inteligence</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)<br>I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2020
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
IEEE Access
ISSN
2169-3536
e-ISSN
—
Svazek periodika
8
Číslo periodika v rámci svazku
2020
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
10
Strana od-do
61989-61998
Kód UT WoS článku
000528692000007
EID výsledku v databázi Scopus
2-s2.0-85083428966