Method for Determining the Resonant Frequencies of Extra High Voltage Power Transmission Line
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F49777513%3A23220%2F23%3A43971014" target="_blank" >RIV/49777513:23220/23:43971014 - isvavai.cz</a>
Výsledek na webu
<a href="http://pe.org.pl/articles/2023/10/7.pdf" target="_blank" >http://pe.org.pl/articles/2023/10/7.pdf</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.15199/48.2023.10.7" target="_blank" >10.15199/48.2023.10.7</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Method for Determining the Resonant Frequencies of Extra High Voltage Power Transmission Line
Popis výsledku v původním jazyce
The paper proposes a mathematical model for determining the resonant frequency of a 750 kV line relative to an unloaded transformer and studies the possibility of overvoltages in 750 kV lines at the 2nd harmonic. A resonant circuit has been compiled to determine the natural frequencies of an ultrahigh voltage power line to analyze the conditions for overvoltages at higher harmonic components. Analytical expressions are obtained to determine the degree of influence of the line parameters' value on the line's resonant frequency. The paper presents the relationship between the operating mode of an ultra-high voltage power line and an autotransformer (transformer) on the conditions for the existence of overvoltages. Analytical expressions for evaluating the influence of the degree of charging power compensation on the values of the mode parameters of the ultra-high voltage power transmission line are given.
Název v anglickém jazyce
Method for Determining the Resonant Frequencies of Extra High Voltage Power Transmission Line
Popis výsledku anglicky
The paper proposes a mathematical model for determining the resonant frequency of a 750 kV line relative to an unloaded transformer and studies the possibility of overvoltages in 750 kV lines at the 2nd harmonic. A resonant circuit has been compiled to determine the natural frequencies of an ultrahigh voltage power line to analyze the conditions for overvoltages at higher harmonic components. Analytical expressions are obtained to determine the degree of influence of the line parameters' value on the line's resonant frequency. The paper presents the relationship between the operating mode of an ultra-high voltage power line and an autotransformer (transformer) on the conditions for the existence of overvoltages. Analytical expressions for evaluating the influence of the degree of charging power compensation on the values of the mode parameters of the ultra-high voltage power transmission line are given.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2023
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Przeglad Elektrotechniczny
ISSN
0033-2097
e-ISSN
2449-9544
Svazek periodika
99
Číslo periodika v rámci svazku
10
Stát vydavatele periodika
PL - Polská republika
Počet stran výsledku
4
Strana od-do
39-42
Kód UT WoS článku
001116614500061
EID výsledku v databázi Scopus
2-s2.0-85175036638