Twelve Flickermeters Comparison Test
Popis výsledku v původním jazyce
The paper describes the test of flicker evaluation made by eleven different types of power quality analyzers. The standard IEC 61000-4-15Ed.2 (Functional and design specification of flickermeter) issued on August 2010 specifies performance testing. Existing flickermeters from different manufacturers may provide different results when processing non-uniform voltage fluctuations. The flickermeters response to voltage varying signals with envelope shape typical for sawmill, heat pump, granulator was tested. Voltage fluctuation caused by operating of this electrical equipment was measured in the real low voltage distribution network by means of the power quality analyzer Topas 1000. Available to the analysis were one-period records of voltage fluctuation.These were simulated on the programmable power voltage source HP6834B in the university lab. All power quality analyzers were together connected on the output of this voltage generator. Additional were made tests according to the IEC 6100
Název v anglickém jazyce
Twelve Flickermeters Comparison Test
Popis výsledku anglicky
The paper describes the test of flicker evaluation made by eleven different types of power quality analyzers. The standard IEC 61000-4-15Ed.2 (Functional and design specification of flickermeter) issued on August 2010 specifies performance testing. Existing flickermeters from different manufacturers may provide different results when processing non-uniform voltage fluctuations. The flickermeters response to voltage varying signals with envelope shape typical for sawmill, heat pump, granulator was tested. Voltage fluctuation caused by operating of this electrical equipment was measured in the real low voltage distribution network by means of the power quality analyzer Topas 1000. Available to the analysis were one-period records of voltage fluctuation.These were simulated on the programmable power voltage source HP6834B in the university lab. All power quality analyzers were together connected on the output of this voltage generator. Additional were made tests according to the IEC 6100
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JB - Senzory, čidla, měření a regulace
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2011
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
IEEE EPQU 2011 Proceedings
ISBN
978-1-4673-0378-1
ISSN
2150-6655
e-ISSN
—
Počet stran výsledku
4
Strana od-do
257-260
Název nakladatele
Institute of Systems and Robotics - University of Coimbra
Místo vydání
Coimbra
Místo konání akce
Lisabon
Datum konání akce
17. 10. 2011
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—