Measurement of illuminance of interior lighting system automatically dimmed to the constant level depending on daylight
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F16%3A86098325" target="_blank" >RIV/61989100:27240/16:86098325 - isvavai.cz</a>
Výsledek na webu
<a href="http://ieeexplore.ieee.org/document/7555604/?reload=true" target="_blank" >http://ieeexplore.ieee.org/document/7555604/?reload=true</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EEEIC.2016.7555604" target="_blank" >10.1109/EEEIC.2016.7555604</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Measurement of illuminance of interior lighting system automatically dimmed to the constant level depending on daylight
Popis výsledku v původním jazyce
The article describes verifying of behaviour of dimming in a regulated lighting system in Smart Home (SH) which was controlled to the constant level of illuminance. The proposed method of measuring was realized as an upgrade for evaluation of curves of interior illuminance caused by daylight. A reference room in SH with a measuring device evaluating illuminance in the places of visual tasks and at the same time scanning illuminance caused by daylight on an outdoor unshadowed horizontal plane was used for measuring. The used measuring device was supplied with a dimmable lighting system of artificial lighting using luminance controller situated on the ceiling of the room in combination with controlling system KNX to reach the constant level of illuminance regarding the influence of both elements of artificial light and daylight. The article shows that there might be difference between the set value of illuminance, which is regulated by a KNX system, and real illuminance in the place of a visual task. Due to this difference, the lighting system may not meet the normative requirements, which is absolutely inacceptable.
Název v anglickém jazyce
Measurement of illuminance of interior lighting system automatically dimmed to the constant level depending on daylight
Popis výsledku anglicky
The article describes verifying of behaviour of dimming in a regulated lighting system in Smart Home (SH) which was controlled to the constant level of illuminance. The proposed method of measuring was realized as an upgrade for evaluation of curves of interior illuminance caused by daylight. A reference room in SH with a measuring device evaluating illuminance in the places of visual tasks and at the same time scanning illuminance caused by daylight on an outdoor unshadowed horizontal plane was used for measuring. The used measuring device was supplied with a dimmable lighting system of artificial lighting using luminance controller situated on the ceiling of the room in combination with controlling system KNX to reach the constant level of illuminance regarding the influence of both elements of artificial light and daylight. The article shows that there might be difference between the set value of illuminance, which is regulated by a KNX system, and real illuminance in the place of a visual task. Due to this difference, the lighting system may not meet the normative requirements, which is absolutely inacceptable.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2016
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
EEEIC 2016 - International Conference on Environment and Electrical Engineering
ISBN
978-1-5090-2320-2
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
1-5
Název nakladatele
Institute of Electrical and Electronics Engineers Inc.
Místo vydání
New York
Místo konání akce
Florence, Italy
Datum konání akce
7. 6. 2016
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—