Measuring of fault distance using the fault locator function of protection relay
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F19%3A10242442" target="_blank" >RIV/61989100:27240/19:10242442 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8778035" target="_blank" >https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8778035</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EPE.2019.8778035" target="_blank" >10.1109/EPE.2019.8778035</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Measuring of fault distance using the fault locator function of protection relay
Popis výsledku v původním jazyce
This article is focused on fault distance measuring with feeder protection relay REF630 from ABB and its function fault locator. This function provides impedance-based fault location. For measuring was used laboratory at Faculty of Electrical Engineering and Computer Science where is laboratory stand with inbuilt REF630 and fault module and where is also available module of transmission network. With those modules there were measured fault distance in case of phase-to-phase fault and phase-to-earth fault for various values of fault resistance. Parameters of typical 11 kV distribution network was set up in protection relay by ABB software PCM600. In case of phase-to-phase fault measured distance corresponded with parameters of model. However, in case of phase-to-earth fault measured fault distance was more than two times lower than our model. Measurement was repeated with parameters of zero sequence reactance equal to positive sequence rectance. Next results corresponded to our model parameters. All results confirmed assumption that higher fault resistance causes lower accuracy of calculated fault distance.
Název v anglickém jazyce
Measuring of fault distance using the fault locator function of protection relay
Popis výsledku anglicky
This article is focused on fault distance measuring with feeder protection relay REF630 from ABB and its function fault locator. This function provides impedance-based fault location. For measuring was used laboratory at Faculty of Electrical Engineering and Computer Science where is laboratory stand with inbuilt REF630 and fault module and where is also available module of transmission network. With those modules there were measured fault distance in case of phase-to-phase fault and phase-to-earth fault for various values of fault resistance. Parameters of typical 11 kV distribution network was set up in protection relay by ABB software PCM600. In case of phase-to-phase fault measured distance corresponded with parameters of model. However, in case of phase-to-earth fault measured fault distance was more than two times lower than our model. Measurement was repeated with parameters of zero sequence reactance equal to positive sequence rectance. Next results corresponded to our model parameters. All results confirmed assumption that higher fault resistance causes lower accuracy of calculated fault distance.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2019
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2019 20th International Scientific Conference on Electric Power Engineering, EPE 2019
ISBN
978-1-72811-333-3
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
249-253
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Kouty nad Desnou
Datum konání akce
15. 5. 2019
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000535890900048