Localization Method for the Resistive Earth Faults in Compensated Network Based on Simultaneous Earth Faults Evaluation
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F00216305%3A26220%2F14%3APU110090" target="_blank" >RIV/00216305:26220/14:PU110090 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Localization Method for the Resistive Earth Faults in Compensated Network Based on Simultaneous Earth Faults Evaluation
Popis výsledku v původním jazyce
This paper is focused on locating earth fault by means of short-term additional earthing of unaffected (healthy) phase and the determination of fault distance based on the distance protection principle. The functionality of above mentioned method was verified during experiments, which were performed in the actual distribution network. The results of the experiments showed that the method of additional earthing of healthy phase is very effective for localization of low resistance and arc earth faults. The line impedance to fault was correctly evaluated by distance protection in the affected feeder during experiments, which in low resistance faults were simulated. In the case of resistive faults and that's already the order of tens of ohms, it is necessary to determine the impedance to the fault location using a different algorithm, which is based on the evaluation of currents and voltage during simultaneous earth faults. Method for evaluation of the line impedance between two simultaneo
Název v anglickém jazyce
Localization Method for the Resistive Earth Faults in Compensated Network Based on Simultaneous Earth Faults Evaluation
Popis výsledku anglicky
This paper is focused on locating earth fault by means of short-term additional earthing of unaffected (healthy) phase and the determination of fault distance based on the distance protection principle. The functionality of above mentioned method was verified during experiments, which were performed in the actual distribution network. The results of the experiments showed that the method of additional earthing of healthy phase is very effective for localization of low resistance and arc earth faults. The line impedance to fault was correctly evaluated by distance protection in the affected feeder during experiments, which in low resistance faults were simulated. In the case of resistive faults and that's already the order of tens of ohms, it is necessary to determine the impedance to the fault location using a different algorithm, which is based on the evaluation of currents and voltage during simultaneous earth faults. Method for evaluation of the line impedance between two simultaneo
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
<a href="/cs/project/LO1210" target="_blank" >LO1210: Energie v podmínkách udržitelného rozvoje (EN-PUR)</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2014
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
The 12th International Conference on Developments in Power System Protection DPSP2014
ISBN
978-1-84919-813-4
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
1-6
Název nakladatele
Neuveden
Místo vydání
Six Hills Way Stevenage Hertfordshire SG1 2AY UK
Místo konání akce
Copenhagen
Datum konání akce
31. 3. 2014
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
—