Analysis of Power Flows in a Building with Nonlinear Loads and a Hybrid Photovoltaic Power Plant with Battery Storage
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F24%3A10256346" target="_blank" >RIV/61989100:27240/24:10256346 - isvavai.cz</a>
Výsledek na webu
<a href="https://ieeexplore.ieee.org/document/10559516" target="_blank" >https://ieeexplore.ieee.org/document/10559516</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/EPE61521.2024.10559516" target="_blank" >10.1109/EPE61521.2024.10559516</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Analysis of Power Flows in a Building with Nonlinear Loads and a Hybrid Photovoltaic Power Plant with Battery Storage
Popis výsledku v původním jazyce
This paper deals with the evaluation of the power quality in a multipurpose building CPIT-TL3 equipped with many non-linear appliances and a hybrid photovoltaic power plant (HPVPP). During the control reading of the power consumption from the electricity meters, discrepancies in the current and power values measured by the main electricity meter of the building and the HPVPP metering system were found. For this reason, measurements were made using power quality analysers. The measurements revealed a significantly distorted current draw with a low power factor. Selectedmeasurement results and their analysis are presented in this paper. Although the significantly distorted current did not affect the quality of the supply voltage, the reduction of current distortion will need to be addressed. The multipurpose building is primarily used for scientific and research purposes; therefore, the distortion of the drawn current should be as low as possible.
Název v anglickém jazyce
Analysis of Power Flows in a Building with Nonlinear Loads and a Hybrid Photovoltaic Power Plant with Battery Storage
Popis výsledku anglicky
This paper deals with the evaluation of the power quality in a multipurpose building CPIT-TL3 equipped with many non-linear appliances and a hybrid photovoltaic power plant (HPVPP). During the control reading of the power consumption from the electricity meters, discrepancies in the current and power values measured by the main electricity meter of the building and the HPVPP metering system were found. For this reason, measurements were made using power quality analysers. The measurements revealed a significantly distorted current draw with a low power factor. Selectedmeasurement results and their analysis are presented in this paper. Although the significantly distorted current did not affect the quality of the supply voltage, the reduction of current distortion will need to be addressed. The multipurpose building is primarily used for scientific and research purposes; therefore, the distortion of the drawn current should be as low as possible.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2024
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceedings of the 2024 24th International Scientific Conference on Electric Power Engineering (EPE) : May 15-17, 2024, Hotel Dlouhé Stráně, Kouty nad Desnou, Czech Republic
ISBN
979-8-3503-4876-7
ISSN
2376-5623
e-ISSN
—
Počet stran výsledku
5
Strana od-do
46-50
Název nakladatele
IEEE
Místo vydání
Piscataway
Místo konání akce
Kouty nad Desnou
Datum konání akce
15. 5. 2024
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
001261334000012