Using synthetic data for pretraining partial discharge detection in overhead transmission lines
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F61989100%3A27240%2F25%3A10259354" target="_blank" >RIV/61989100:27240/25:10259354 - isvavai.cz</a>
Nalezeny alternativní kódy
RIV/61989100:27730/25:10259354
Výsledek na webu
<a href="https://www.nature.com/articles/s41598-025-32642-2" target="_blank" >https://www.nature.com/articles/s41598-025-32642-2</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1038/s41598-025-32642-2" target="_blank" >10.1038/s41598-025-32642-2</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Using synthetic data for pretraining partial discharge detection in overhead transmission lines
Popis výsledku v původním jazyce
Accurate detection of partial discharges (PDs) in medium-voltage overhead transmission lines is critical for preemptive maintenance and avoiding costly outages, yet it is challenged by scarce labeled data and pervasive electromagnetic interference. This paper investigates a hybrid simulation-and-data-driven framework in which synthetically generated PD signals are used to pretrain deep neural networks and are subsequently fine-tuned on a limited set of real overhead-line measurements. The synthetic pipeline systematically varies PD repetition rates, amplitude distributions, vegetation-contact scenarios, and noise conditions, producing diverse time-series and spectrogram-like representations that approximate real operating environments. We conduct a comprehensive ablation study across multiple architectures—Convolutional Neural Networks (CNNs), a Vision Transformer (ViT), and a Long Short-Term Memory (LSTM) network—and analyze their sensitivity to granular sweeps of synthetic-data parameters. CNN-based models decisively outperform ViT and LSTM counterparts on the spectrogram-based classification task, while ViT and LSTM fail to learn meaningful representation. For the successful CNNs, pretraining on carefully parameterized synthetic datasets—particularly those reflecting higher PD activity, such as our Datasets 3 and 4—consistently improves downstream performance on real data, boosting the Matthews Correlation Coefficient (MCC) on imbalanced, cost-sensitive test sets by roughly 10–20% compared with training from scratch. At the same time, we show that poorly aligned synthetic data can degrade generalization, underscoring the need for accurate noise calibration and domain-aligned simulation. Overall, the results confirm that (i) architectural choice is pivotal for PD detection in overhead lines and (ii) well-designed synthetic data is a powerful, practical lever for achieving reliable and cost-effective PD monitoring when real labeled data are limited. © The Author(s) 2025.
Název v anglickém jazyce
Using synthetic data for pretraining partial discharge detection in overhead transmission lines
Popis výsledku anglicky
Accurate detection of partial discharges (PDs) in medium-voltage overhead transmission lines is critical for preemptive maintenance and avoiding costly outages, yet it is challenged by scarce labeled data and pervasive electromagnetic interference. This paper investigates a hybrid simulation-and-data-driven framework in which synthetically generated PD signals are used to pretrain deep neural networks and are subsequently fine-tuned on a limited set of real overhead-line measurements. The synthetic pipeline systematically varies PD repetition rates, amplitude distributions, vegetation-contact scenarios, and noise conditions, producing diverse time-series and spectrogram-like representations that approximate real operating environments. We conduct a comprehensive ablation study across multiple architectures—Convolutional Neural Networks (CNNs), a Vision Transformer (ViT), and a Long Short-Term Memory (LSTM) network—and analyze their sensitivity to granular sweeps of synthetic-data parameters. CNN-based models decisively outperform ViT and LSTM counterparts on the spectrogram-based classification task, while ViT and LSTM fail to learn meaningful representation. For the successful CNNs, pretraining on carefully parameterized synthetic datasets—particularly those reflecting higher PD activity, such as our Datasets 3 and 4—consistently improves downstream performance on real data, boosting the Matthews Correlation Coefficient (MCC) on imbalanced, cost-sensitive test sets by roughly 10–20% compared with training from scratch. At the same time, we show that poorly aligned synthetic data can degrade generalization, underscoring the need for accurate noise calibration and domain-aligned simulation. Overall, the results confirm that (i) architectural choice is pivotal for PD detection in overhead lines and (ii) well-designed synthetic data is a powerful, practical lever for achieving reliable and cost-effective PD monitoring when real labeled data are limited. © The Author(s) 2025.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
10201 - Computer sciences, information science, bioinformathics (hardware development to be 2.2, social aspect to be 5.8)
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2025
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Scientific Reports
ISSN
2045-2322
e-ISSN
2045-2322
Svazek periodika
15
Číslo periodika v rámci svazku
1
Stát vydavatele periodika
GB - Spojené království Velké Británie a Severního Irska
Počet stran výsledku
24
Strana od-do
15
Kód UT WoS článku
001651181400021
EID výsledku v databázi Scopus
2-s2.0-105026217746