Analysis of impact of plate air-to-air recovery untightness on its thermal and mass balance
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21110%2F08%3A00175211" target="_blank" >RIV/68407700:21110/08:00175211 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Analysis of impact of plate air-to-air recovery untightness on its thermal and mass balance
Popis výsledku v původním jazyce
The article deals with the issue of determination of leaks from a recovery heat exchanger using secondary heat contained in ventilation air and an analysis of impact of leak upon the nature of ventilation system, shared thermal flows, thermal and operational efficiency of the exchanger. The verification of the hypothesis based on results of a theoretical analysis of the issue was accomplished at an operational metering of a prototype of ventilation unit provided with a plate exchanger in calf breeding house after the installation of the unit and, furthermore, after 9 months of the operation of the unit. Results of the verification confirmed the conclusions of the theoretical analysis of the issue. They demonstrated that the new unit added 21.1 to 30.8%of extracted air to the atmospheric air supplied to the breeding house. Heat output exchanged during process of fresh air contamination varied between 5.15 to 11.42 kW.
Název v anglickém jazyce
Analysis of impact of plate air-to-air recovery untightness on its thermal and mass balance
Popis výsledku anglicky
The article deals with the issue of determination of leaks from a recovery heat exchanger using secondary heat contained in ventilation air and an analysis of impact of leak upon the nature of ventilation system, shared thermal flows, thermal and operational efficiency of the exchanger. The verification of the hypothesis based on results of a theoretical analysis of the issue was accomplished at an operational metering of a prototype of ventilation unit provided with a plate exchanger in calf breeding house after the installation of the unit and, furthermore, after 9 months of the operation of the unit. Results of the verification confirmed the conclusions of the theoretical analysis of the issue. They demonstrated that the new unit added 21.1 to 30.8%of extracted air to the atmospheric air supplied to the breeding house. Heat output exchanged during process of fresh air contamination varied between 5.15 to 11.42 kW.
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2008
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Scientia Agriculturae Bohemica
ISSN
1211-3174
e-ISSN
—
Svazek periodika
39
Číslo periodika v rámci svazku
3
Stát vydavatele periodika
CZ - Česká republika
Počet stran výsledku
6
Strana od-do
—
Kód UT WoS článku
—
EID výsledku v databázi Scopus
—