Proudění ve dvojité prosklené fasádě
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21220%2F08%3A02147824" target="_blank" >RIV/68407700:21220/08:02147824 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Flow in a Double Skin Facade
Popis výsledku v původním jazyce
The paper deals with CFD modeling and simulations of a double-skin facade in the Fluent software. The analysis of particular processes related to the double-skin facade performance for correct definition of boundyry conditions. Some of the processes weretested on simple exemplars like modeling of solar radiation and heat gains, natural convection on a vertical channel and the impact of blinds on airflow in a double-skin facade. Air temperature measurements were carried out in a real building with a double-skin facade in order to partly validate the simulations. The measured data can significantly differ from the simulation depending on the ratio between solar radiation energy obsorbed by the facade and energy scattered out to the ambient environment.The ratio between the two portions must be prescribed a priori in the model. In this context, a reliable model calibration should be based on a series of experiments.
Název v anglickém jazyce
Flow in a Double Skin Facade
Popis výsledku anglicky
The paper deals with CFD modeling and simulations of a double-skin facade in the Fluent software. The analysis of particular processes related to the double-skin facade performance for correct definition of boundyry conditions. Some of the processes weretested on simple exemplars like modeling of solar radiation and heat gains, natural convection on a vertical channel and the impact of blinds on airflow in a double-skin facade. Air temperature measurements were carried out in a real building with a double-skin facade in order to partly validate the simulations. The measured data can significantly differ from the simulation depending on the ratio between solar radiation energy obsorbed by the facade and energy scattered out to the ambient environment.The ratio between the two portions must be prescribed a priori in the model. In this context, a reliable model calibration should be based on a series of experiments.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2008
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Simulace budov a techniky prostředí
ISBN
978-80-254-3373-7
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
—
Název nakladatele
IBPSA-CZ
Místo vydání
Praha
Místo konání akce
Brno
Datum konání akce
6. 11. 2008
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—