Detection of Disturbance of Working Conditions of Current Transformer in Energy Meters for Reduction of Unauthorized Current Consumption
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F09%3A00159053" target="_blank" >RIV/68407700:21230/09:00159053 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Detection of Disturbance of Working Conditions of Current Transformer in Energy Meters for Reduction of Unauthorized Current Consumption
Popis výsledku v původním jazyce
Current transformers can be very easily affected by dc component of measured current. The behavior of such transformers can be different in comparison with normal conditions. The errors of power measurements arise in order of units of percent and can beboth positive and negative according to the type of load for some type of current transformers. The errors are mainly caused by change of phase shift between primary and secondary current. The source of the problem is dc magnetic flux in the ferromagnetic core of the current transformer. The presence of dc magnetic field in ferromagnetic core of current transformer can be, in some cases, detected by analyzing the frequency spectrum of current signal using a microcontroller, usually by measuring the second harmonic. According to these results the energy meter is able to decide about possibility of unauthorized current consumption.
Název v anglickém jazyce
Detection of Disturbance of Working Conditions of Current Transformer in Energy Meters for Reduction of Unauthorized Current Consumption
Popis výsledku anglicky
Current transformers can be very easily affected by dc component of measured current. The behavior of such transformers can be different in comparison with normal conditions. The errors of power measurements arise in order of units of percent and can beboth positive and negative according to the type of load for some type of current transformers. The errors are mainly caused by change of phase shift between primary and secondary current. The source of the problem is dc magnetic flux in the ferromagnetic core of the current transformer. The presence of dc magnetic field in ferromagnetic core of current transformer can be, in some cases, detected by analyzing the frequency spectrum of current signal using a microcontroller, usually by measuring the second harmonic. According to these results the energy meter is able to decide about possibility of unauthorized current consumption.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2009
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
PEDS 2009 - The Eighth International Conference on Power Electronics and Drive Systems
ISBN
978-1-4244-4166-2
ISSN
—
e-ISSN
—
Počet stran výsledku
4
Strana od-do
—
Název nakladatele
IEEE Power Electronics Society - PELS
Místo vydání
Taipei
Místo konání akce
Taipei
Datum konání akce
2. 11. 2009
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000277469700052