Drawback of Using Double Core Current Transformers in Static Watt-Hour Meters
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F09%3A00160009" target="_blank" >RIV/68407700:21230/09:00160009 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Drawback of Using Double Core Current Transformers in Static Watt-Hour Meters
Popis výsledku v původním jazyce
This article deals with dual core current transformers that are used in some modern static watt-hour meters where they should substitute the more expensive DC tolerant current transformer with linear hysteresis loop. It describes the problem of power consumption measurement on inductive or capacitive loads where some DC magnetic field is applied. In this case the core with high permeability is saturated and operating point is moved on hysteresis loop of low permeability core. Then additional errors occur and the sign of the error can be both positive and negative depending on load type. Dimension of errors can be in order from units up to tens of per cents and it relies on power factor and DC magnetic field. Explanation of this problem is described inthe article as well as some results of measurements and comparison with theoretical computation.
Název v anglickém jazyce
Drawback of Using Double Core Current Transformers in Static Watt-Hour Meters
Popis výsledku anglicky
This article deals with dual core current transformers that are used in some modern static watt-hour meters where they should substitute the more expensive DC tolerant current transformer with linear hysteresis loop. It describes the problem of power consumption measurement on inductive or capacitive loads where some DC magnetic field is applied. In this case the core with high permeability is saturated and operating point is moved on hysteresis loop of low permeability core. Then additional errors occur and the sign of the error can be both positive and negative depending on load type. Dimension of errors can be in order from units up to tens of per cents and it relies on power factor and DC magnetic field. Explanation of this problem is described inthe article as well as some results of measurements and comparison with theoretical computation.
Klasifikace
Druh
J<sub>x</sub> - Nezařazeno - Článek v odborném periodiku (Jimp, Jsc a Jost)
CEP obor
JA - Elektronika a optoelektronika, elektrotechnika
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
Z - Vyzkumny zamer (s odkazem do CEZ)
Ostatní
Rok uplatnění
2009
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Sensor Letters
ISSN
1546-198X
e-ISSN
—
Svazek periodika
7
Číslo periodika v rámci svazku
3
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
3
Strana od-do
—
Kód UT WoS článku
000271193300044
EID výsledku v databázi Scopus
—