Ferroresonance Phenomena in Medium Voltage Systems
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F15%3A00232561" target="_blank" >RIV/68407700:21230/15:00232561 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Ferroresonance Phenomena in Medium Voltage Systems
Popis výsledku v původním jazyce
The paper deals with the analysis of the formation of ferroresonance in MV systems. The analysis is focused on ferroresonance caused by instrument voltage transformer (IVT) connected to the outlet of the tertiary winding 10,5 kV autotransformer 400/110 kV. A non-linear element in this case is the magnetic circuit of IVT Ferro-resonance, in this case exhibits similar to the imperfect ground connection. The two phases may arise overvoltages in two phases and undervoltage in one phase. The rate of these adverse events is given by the initial conditions and load of switched circuits when circuit is switched on. Similarly, other exhibit nonlinear chaotic circuits. The main adverse effects include overvoltage that can damage the power system components wellas a significant harmonic distortion. For prevent this problem the authors conducted the case study resonant circuit as a whole. In this case it is magnetic circuit of the IVT, in which saturate a hysteresis the magnetic flux depending on
Název v anglickém jazyce
Ferroresonance Phenomena in Medium Voltage Systems
Popis výsledku anglicky
The paper deals with the analysis of the formation of ferroresonance in MV systems. The analysis is focused on ferroresonance caused by instrument voltage transformer (IVT) connected to the outlet of the tertiary winding 10,5 kV autotransformer 400/110 kV. A non-linear element in this case is the magnetic circuit of IVT Ferro-resonance, in this case exhibits similar to the imperfect ground connection. The two phases may arise overvoltages in two phases and undervoltage in one phase. The rate of these adverse events is given by the initial conditions and load of switched circuits when circuit is switched on. Similarly, other exhibit nonlinear chaotic circuits. The main adverse effects include overvoltage that can damage the power system components wellas a significant harmonic distortion. For prevent this problem the authors conducted the case study resonant circuit as a whole. In this case it is magnetic circuit of the IVT, in which saturate a hysteresis the magnetic flux depending on
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
JE - Nejaderná energetika, spotřeba a užití energie
OECD FORD obor
—
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
19th International Symposium on High Voltage Engineering
ISBN
978-80-261-0477-3
ISSN
—
e-ISSN
—
Počet stran výsledku
5
Strana od-do
—
Název nakladatele
University of West Bohemia
Místo vydání
Pilsen
Místo konání akce
Pilsen
Datum konání akce
23. 8. 2015
Typ akce podle státní příslušnosti
EUR - Evropská akce
Kód UT WoS článku
—