Use of Directional Overcurrent Protection Scheme for Distributed Generation Systems
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F15%3A00235844" target="_blank" >RIV/68407700:21230/15:00235844 - isvavai.cz</a>
Výsledek na webu
—
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Use of Directional Overcurrent Protection Scheme for Distributed Generation Systems
Popis výsledku v původním jazyce
This paper proposes protection scheme of distributed generation systems based on adaptive directional overcurrent protections with inverse-time characteristics. First, protection of distributed generation system is compared with classical conception system and individual differences in protection settings are discussed. Proposed protection scheme is composed of individual protections connected by communication lines. These lines inform protections about the present network configuration and in the case of changes in protected system new protection setting is computed. Use of directional overcurrent protections with inverse-time characteristics allows us to create protection settings resistant to small variations in short-circuit currents. This paper describes protection coordination for an example of network configuration. For the correct setting of inverse-time characteristics, and also its validation, short-circuit conditions in every node of network are required, and program SimPoruchy 2.0 was used. Program allows for quick and wellarranged output of short-circuit conditions of network and also for simulation of mentioned protection types.
Název v anglickém jazyce
Use of Directional Overcurrent Protection Scheme for Distributed Generation Systems
Popis výsledku anglicky
This paper proposes protection scheme of distributed generation systems based on adaptive directional overcurrent protections with inverse-time characteristics. First, protection of distributed generation system is compared with classical conception system and individual differences in protection settings are discussed. Proposed protection scheme is composed of individual protections connected by communication lines. These lines inform protections about the present network configuration and in the case of changes in protected system new protection setting is computed. Use of directional overcurrent protections with inverse-time characteristics allows us to create protection settings resistant to small variations in short-circuit currents. This paper describes protection coordination for an example of network configuration. For the correct setting of inverse-time characteristics, and also its validation, short-circuit conditions in every node of network are required, and program SimPoruchy 2.0 was used. Program allows for quick and wellarranged output of short-circuit conditions of network and also for simulation of mentioned protection types.
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
20704 - Energy and fuels
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2015
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
2015 16th International Scientific Conference on Electric Power Engineering (EPE)
ISBN
978-1-4673-6788-2
ISSN
—
e-ISSN
2376-5623
Počet stran výsledku
6
Strana od-do
325-330
Název nakladatele
VŠB - Technical University of Ostrava
Místo vydání
Ostrava
Místo konání akce
Kouty nad Desnou
Datum konání akce
20. 5. 2015
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000377548600063