Classification of Multiple Partial Discharge Sources Using Time-Frequency Analysis and Deep Learning
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F25%3A00384611" target="_blank" >RIV/68407700:21230/25:00384611 - isvavai.cz</a>
Výsledek na webu
<a href="https://doi.org/10.3390/app15105455" target="_blank" >https://doi.org/10.3390/app15105455</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.3390/app15105455" target="_blank" >10.3390/app15105455</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Classification of Multiple Partial Discharge Sources Using Time-Frequency Analysis and Deep Learning
Popis výsledku v původním jazyce
Partial discharge (PD) analysis is critical for diagnosing insulation degradation in high-voltage equipment. While conventional methods struggle with multi-source PD classification due to signal overlap and noise, this study proposes a hybrid approach combining five time–frequency analysis (TFA) techniques with deep learning (GoogLeNet for simulation, ResNet50 for experiments). PD data are generated through Finite Element Method (FEM) simulations and validated via laboratory experiments. The Scatter Wavelet Transform (SWT) achieves 96.67% accuracy (F1-score: 0.967) in simulation and perfect 100% accuracy (F1-score: 1.000) in experiments, outperforming other TFAs like HHT (70.00% experimental accuracy). The Wigner–Ville Distribution (WVD) also shows strong experimental performance (94.74% accuracy, AUC: 0.947), though its computational complexity limits real-time use. These results demonstrate the SWT’s superiority in handling real-world noise and multi-source PD signals, providing a robust framework for insulation diagnostics in power systems.
Název v anglickém jazyce
Classification of Multiple Partial Discharge Sources Using Time-Frequency Analysis and Deep Learning
Popis výsledku anglicky
Partial discharge (PD) analysis is critical for diagnosing insulation degradation in high-voltage equipment. While conventional methods struggle with multi-source PD classification due to signal overlap and noise, this study proposes a hybrid approach combining five time–frequency analysis (TFA) techniques with deep learning (GoogLeNet for simulation, ResNet50 for experiments). PD data are generated through Finite Element Method (FEM) simulations and validated via laboratory experiments. The Scatter Wavelet Transform (SWT) achieves 96.67% accuracy (F1-score: 0.967) in simulation and perfect 100% accuracy (F1-score: 1.000) in experiments, outperforming other TFAs like HHT (70.00% experimental accuracy). The Wigner–Ville Distribution (WVD) also shows strong experimental performance (94.74% accuracy, AUC: 0.947), though its computational complexity limits real-time use. These results demonstrate the SWT’s superiority in handling real-world noise and multi-source PD signals, providing a robust framework for insulation diagnostics in power systems.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2025
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Classification of Multiple Partial Discharge Sources Using Time-Frequency Analysis and Deep Learning
ISSN
2076-3417
e-ISSN
2076-3417
Svazek periodika
15
Číslo periodika v rámci svazku
10
Stát vydavatele periodika
CH - Švýcarská konfederace
Počet stran výsledku
26
Strana od-do
—
Kód UT WoS článku
001495888300001
EID výsledku v databázi Scopus
2-s2.0-105006700391