Monitoring and Analysing Changes in Temperature and Energy in the Ground with Installed Horizontal Ground Heat Exchangers
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F60460709%3A41310%2F16%3A70666" target="_blank" >RIV/60460709:41310/16:70666 - isvavai.cz</a>
Výsledek na webu
<a href="http://dx.doi.org/10.3390/en9080555" target="_blank" >http://dx.doi.org/10.3390/en9080555</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.3390/en9080555" target="_blank" >10.3390/en9080555</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Monitoring and Analysing Changes in Temperature and Energy in the Ground with Installed Horizontal Ground Heat Exchangers
Popis výsledku v původním jazyce
The objective of this work was to monitor and analyse temperature changes in the ground with installed linear and Slinky-type horizontal ground heat exchangers (HGHEs), used as low-potential heat pump energy sources. Specific heat flows and specific energies extracted from the ground during the heating season were also measured and compared. The verification results showed that the average daily ground temperatures with the two HGHEs are primarily affected by the temperature of the ambient environment. The ground temperatures were higher than ambient temperature during most of the heating season, were only seldom below zero, and were higher by an average 1.97 0.77 K in the ground with the linear HGHE than in the ground with the Slinky-type HGHE. Additionally, the specific thermal output extracted from the ground by the HGHE was higher by 8.45 16.57 W/m2 with the linear system than with the Slinky system. The specific energies extracted from the ground over the whole heating season were 110.15 kWh/
Název v anglickém jazyce
Monitoring and Analysing Changes in Temperature and Energy in the Ground with Installed Horizontal Ground Heat Exchangers
Popis výsledku anglicky
The objective of this work was to monitor and analyse temperature changes in the ground with installed linear and Slinky-type horizontal ground heat exchangers (HGHEs), used as low-potential heat pump energy sources. Specific heat flows and specific energies extracted from the ground during the heating season were also measured and compared. The verification results showed that the average daily ground temperatures with the two HGHEs are primarily affected by the temperature of the ambient environment. The ground temperatures were higher than ambient temperature during most of the heating season, were only seldom below zero, and were higher by an average 1.97 0.77 K in the ground with the linear HGHE than in the ground with the Slinky-type HGHE. Additionally, the specific thermal output extracted from the ground by the HGHE was higher by 8.45 16.57 W/m2 with the linear system than with the Slinky system. The specific energies extracted from the ground over the whole heating season were 110.15 kWh/
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20704 - Energy and fuels
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2016
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
Energies
ISSN
1996-1073
e-ISSN
—
Svazek periodika
9
Číslo periodika v rámci svazku
8
Stát vydavatele periodika
CZ - Česká republika
Počet stran výsledku
13
Strana od-do
1-13
Kód UT WoS článku
000383547400001
EID výsledku v databázi Scopus
2-s2.0-84982899730