HORIZONTAL GROUND HEAT EXCHANGERS - LOW-TEMPERATURE ENERGY SOURCE
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F60460709%3A41310%2F19%3A81683" target="_blank" >RIV/60460709:41310/19:81683 - isvavai.cz</a>
Výsledek na webu
<a href="https://2019.tae-conference.cz/proceeding/TAE2019-002-Radomir-Adamovsky.pdf" target="_blank" >https://2019.tae-conference.cz/proceeding/TAE2019-002-Radomir-Adamovsky.pdf</a>
DOI - Digital Object Identifier
—
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
HORIZONTAL GROUND HEAT EXCHANGERS - LOW-TEMPERATURE ENERGY SOURCE
Popis výsledku v původním jazyce
The aim of this paper is to analyse and compare the temperatures of heat carrier fluids, thermal resistances, specific outputs and extracted energies for horizontal ground heat exchangers used in the function of low-temperature energy source for heat pumps. Linear and Slinky type horizontal ground heat exchangers, the most commonly used ones in Europe, were verified. The temperatures of the heat carrier fluids did not reach negative temperatures in the two horizontal exchangers throughout the monitored period. The results of the verification indicated that, in terms of the monitored parameters, the linear horizontal exchanger seemed to be more effective than the Slinky type. The temperatures of the heat carrier fluid were on average higher at the linear exchanger by 1,43 +/- 2,12 K, with a specific output of 5,76 W per 1 m(2) of the heat exchange surface. The thermal resistance was higher at the Slinky than at the linear exchanger by 50%
Název v anglickém jazyce
HORIZONTAL GROUND HEAT EXCHANGERS - LOW-TEMPERATURE ENERGY SOURCE
Popis výsledku anglicky
The aim of this paper is to analyse and compare the temperatures of heat carrier fluids, thermal resistances, specific outputs and extracted energies for horizontal ground heat exchangers used in the function of low-temperature energy source for heat pumps. Linear and Slinky type horizontal ground heat exchangers, the most commonly used ones in Europe, were verified. The temperatures of the heat carrier fluids did not reach negative temperatures in the two horizontal exchangers throughout the monitored period. The results of the verification indicated that, in terms of the monitored parameters, the linear horizontal exchanger seemed to be more effective than the Slinky type. The temperatures of the heat carrier fluid were on average higher at the linear exchanger by 1,43 +/- 2,12 K, with a specific output of 5,76 W per 1 m(2) of the heat exchange surface. The thermal resistance was higher at the Slinky than at the linear exchanger by 50%
Klasifikace
Druh
D - Stať ve sborníku
CEP obor
—
OECD FORD obor
40101 - Agriculture
Návaznosti výsledku
Projekt
—
Návaznosti
S - Specificky vyzkum na vysokych skolach
Ostatní
Rok uplatnění
2019
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název statě ve sborníku
Proceeding of 7th International Conference on Trends in Agricultural Engineering 2019
ISBN
978-80-213-2953-9
ISSN
—
e-ISSN
—
Počet stran výsledku
6
Strana od-do
8-13
Název nakladatele
Czech Univ Life Sci, Fac Engn
Místo vydání
Prague
Místo konání akce
Prague
Datum konání akce
17. 9. 2019
Typ akce podle státní příslušnosti
WRD - Celosvětová akce
Kód UT WoS článku
000521578500002