Virtual Impedance Sliding Mode Control-Based MMC Circulating Current Suppressing Strategy
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F19%3A00330807" target="_blank" >RIV/68407700:21230/19:00330807 - isvavai.cz</a>
Výsledek na webu
<a href="https://doi.org/10.1109/ACCESS.2019.2900471" target="_blank" >https://doi.org/10.1109/ACCESS.2019.2900471</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/ACCESS.2019.2900471" target="_blank" >10.1109/ACCESS.2019.2900471</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
Virtual Impedance Sliding Mode Control-Based MMC Circulating Current Suppressing Strategy
Popis výsledku v původním jazyce
The device rated capacity, system loss, and cost of a modular multilevel converter are proportional to the circulating current value. In order to enhance suppressing the second order harmonic component of circulating current and improve the dynamic response of the system, a novel circulating current suppressing strategy based on virtual impedance sliding mode control (VI-SMC-CCS) is proposed. This paper first analyzes the essential CCS mechanism, then presents a circulating current decoupling model using a state feedback linearization method, improving the system accuracy. Moreover, the sliding mode control and virtual impedance loop are introduced to strengthen system robustness. Different circulating current suppressing strategies are compared by simulation, the results demonstrate the correctness of the VI-SMC-CCS, which not only effectively reduces the second order harmonic component of the circulating current, but also improves the stability, reliability, and rapidity of the system.
Název v anglickém jazyce
Virtual Impedance Sliding Mode Control-Based MMC Circulating Current Suppressing Strategy
Popis výsledku anglicky
The device rated capacity, system loss, and cost of a modular multilevel converter are proportional to the circulating current value. In order to enhance suppressing the second order harmonic component of circulating current and improve the dynamic response of the system, a novel circulating current suppressing strategy based on virtual impedance sliding mode control (VI-SMC-CCS) is proposed. This paper first analyzes the essential CCS mechanism, then presents a circulating current decoupling model using a state feedback linearization method, improving the system accuracy. Moreover, the sliding mode control and virtual impedance loop are introduced to strengthen system robustness. Different circulating current suppressing strategies are compared by simulation, the results demonstrate the correctness of the VI-SMC-CCS, which not only effectively reduces the second order harmonic component of the circulating current, but also improves the stability, reliability, and rapidity of the system.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
<a href="/cs/project/LTACH17001" target="_blank" >LTACH17001: Studie výkonné části "energy routeru" a strategie jeho řízení</a><br>
Návaznosti
P - Projekt vyzkumu a vyvoje financovany z verejnych zdroju (s odkazem do CEP)
Ostatní
Rok uplatnění
2019
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
IEEE Access
ISSN
2169-3536
e-ISSN
2169-3536
Svazek periodika
7
Číslo periodika v rámci svazku
March
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
12
Strana od-do
26229-26240
Kód UT WoS článku
000461877000001
EID výsledku v databázi Scopus
2-s2.0-85063005782