A New Algorithm for Detecting Failure to Clear Mode of Circuit Breakers Using Fundamental Frequency Component of Voltage Signals
Identifikátory výsledku
Kód výsledku v IS VaVaI
<a href="https://www.isvavai.cz/riv?ss=detail&h=RIV%2F68407700%3A21230%2F20%3A00341380" target="_blank" >RIV/68407700:21230/20:00341380 - isvavai.cz</a>
Výsledek na webu
<a href="https://doi.org/10.1109/TPWRD.2019.2927102" target="_blank" >https://doi.org/10.1109/TPWRD.2019.2927102</a>
DOI - Digital Object Identifier
<a href="http://dx.doi.org/10.1109/TPWRD.2019.2927102" target="_blank" >10.1109/TPWRD.2019.2927102</a>
Alternativní jazyky
Jazyk výsledku
angličtina
Název v původním jazyce
A New Algorithm for Detecting Failure to Clear Mode of Circuit Breakers Using Fundamental Frequency Component of Voltage Signals
Popis výsledku v původním jazyce
This paper introduces a new algorithm for the early detection of abnormal arcing conditions of circuit breakers (CBs). Any interruption with a higher arcing time compared to maximum permissible arcing time of CB is defined as a CB failure to clear mode. Measuring CB arcing time is not easy because there is no control on the mechanical opening and closing instants of CB contacts. Nevertheless, there is a correlation between the spectral energy densities of CB arcing voltages and arcing times of CB. This correlation is used by calculating the spectral energy densities of the instantaneous system voltage and the instantaneous CB voltage across its terminals utilizing discrete Fourier transform for two periods of the system frequency. The difference between the spectral energy densities at the fundamental frequency is defined as a criterion for identifying a failure to clear mode. Whenever this criterion exceeds a predefined trip level, it indicates the occurrence of a failure to clear mode. In this situation, a trip signal is initiated for adjacent CBs to isolate the faulted CB and the fault. The results obtained from computer simulations and measurements show that the algorithm discriminates between normal and abnormal arcing conditions of CB.
Název v anglickém jazyce
A New Algorithm for Detecting Failure to Clear Mode of Circuit Breakers Using Fundamental Frequency Component of Voltage Signals
Popis výsledku anglicky
This paper introduces a new algorithm for the early detection of abnormal arcing conditions of circuit breakers (CBs). Any interruption with a higher arcing time compared to maximum permissible arcing time of CB is defined as a CB failure to clear mode. Measuring CB arcing time is not easy because there is no control on the mechanical opening and closing instants of CB contacts. Nevertheless, there is a correlation between the spectral energy densities of CB arcing voltages and arcing times of CB. This correlation is used by calculating the spectral energy densities of the instantaneous system voltage and the instantaneous CB voltage across its terminals utilizing discrete Fourier transform for two periods of the system frequency. The difference between the spectral energy densities at the fundamental frequency is defined as a criterion for identifying a failure to clear mode. Whenever this criterion exceeds a predefined trip level, it indicates the occurrence of a failure to clear mode. In this situation, a trip signal is initiated for adjacent CBs to isolate the faulted CB and the fault. The results obtained from computer simulations and measurements show that the algorithm discriminates between normal and abnormal arcing conditions of CB.
Klasifikace
Druh
J<sub>imp</sub> - Článek v periodiku v databázi Web of Science
CEP obor
—
OECD FORD obor
20201 - Electrical and electronic engineering
Návaznosti výsledku
Projekt
—
Návaznosti
I - Institucionalni podpora na dlouhodoby koncepcni rozvoj vyzkumne organizace
Ostatní
Rok uplatnění
2020
Kód důvěrnosti údajů
S - Úplné a pravdivé údaje o projektu nepodléhají ochraně podle zvláštních právních předpisů
Údaje specifické pro druh výsledku
Název periodika
IEEE Transactions on Power Delivery
ISSN
0885-8977
e-ISSN
1937-4208
Svazek periodika
35
Číslo periodika v rámci svazku
2
Stát vydavatele periodika
US - Spojené státy americké
Počet stran výsledku
8
Strana od-do
794-801
Kód UT WoS článku
000522350600037
EID výsledku v databázi Scopus
2-s2.0-85083111015